SIMPLEX 4100 EWIS
INSTALLATION MANUAL
Figure 7 Mounting the door on the Back Box
14. Close and lock the panel door.
2.3 INSTALL AND TAG ALL SYSTEM WIRING.
• See the SYSTEM POINT SUMMARY Report (Table 7) and the appropriate
page in the 4100 Field Wiring Diagram (841-731).
2.4 INSTALL THE PERIPHERAL DEVICES AND E.O.L. RESISTORS.
• See Section 3 Field Terminations for details of terminating peripheral
devices.
• See the Point Type column in the SYSTEM POINT SUMMARY Report for
device type.
NOTES:
A. The 748-200 System Hardware envelope contains the required
resistors.
• 3.3K (monitor zone) resistors are colour coded orange, orange, red
(and have a gold tolerance band); 10K (Notification appliance [signal]
circuit) resistors are colour coded brown, black, orange (and also have
a gold tolerance band).
• Resistors other than those described above will be used by the
Simplex Technical Representative (T.R.) during installation checkout.
B. Wire peripherals in accordance with the appropriate 4100 Field Wiring
Diagram (841-731).
C. Use a small screwdriver or ball point pen to set device address switches.
D. After setting the device address, mark the device's address label
(Figure 9) to agree with the address switches.
Document No.: 4100-M011
March 1998
Page 13
Issue 1.0