SIMPLEX 4100 EWIS
INSTALLATION MANUAL

2. INSTALLATION PROCEDURE

2.1 CABINET INSTALLATION

The 4100 EWIS system cabinet should be mounted such that all indicators and
controls are not less than 750 mm and not more than 1850 mm from the floor level.

2.1.1 Surface Mount

For surface mount, 4 bolts secure the Back Box cabinet or screws through predrilled
12 mm holes on the rear of the cabinet.

2.1.2 Recess Mount

For a recess mounting of the Back Box cabinet allow a cut out equal to the size of
the cabinet plus 10mm all round clearance.

2.2 CARD INSTALLATION

The following instructions provide a systematic method for installing system printed
circuit boards (or cards) in a 4100 EWIS system if these are not already installed.
STEP #
ACTION
Open each system card box and remove the system cards from the
1.
container.
Install the master control card.
2.
Install the RS-232/2120 Communications Card or the RS-485 Network
3.
Interface Card.
Install the daughter cards.
4.
Verify all cabling and wiring harness connections. Refer to Simplex field
5.
wiring Diagram (Part No. 841-731).
Verify all system wiring is terminated at specified terminal locations as
6.
specified by Simplex Field Wiring Diagram (Part No. 841-731)
Perform a complete system test of all installed devices.
7.
Install and secure the retainer panel on the back box.
8.
Mount the door on the back box.
9.
Document No.: 4100-M011
March 1998
Page 3
Issue 1.0