6.3.4

Setting DO output status

Set the DO output status to RESET or HOLD, which is one of the output states of the output
module arising in case of an error on a remote I/O line. If it is set to RESET, the output is
zeroized or zerofilled. If it is set to HOLD, the value immediately before the error is output.
CPU module
LQP000
LADDER
RUN
MODE
NORM
CPU RUN
PROTECT
ON
RESET
HITACHI
S10mini
RI/O module
LQS000
HITACHI
HSC-1000
Output
(when RESET is set)
Output
(when HOLD is set)
CPU-S
STOP
SIMU
OFF
Jumper plugs
1
2
3
4
5
6
7
RI/O
RI/O
U
ST.NO
L
A2
A3
Terminal block
Duration during
which the remote
I/O line is broken
Zero
The previous
value is
maintained.
Break
Setting of jumper plug 2
Item to set
Connected
Output mode
RESET
(Factory setting)
Connection of terminals
Item to set
Not connected
Output mode
RESET
(Factory setting)
- 61 -
6 SETTING
The cause of the
error is corrected.
Not connected
HOLD
Connected
A2 (COM)
A3 (HOLD)
HOLD