Run (Ladder Program Execution) Mode; Simu (Simulated Ladder Program Execution) Mode; Reset Mode - Hitachi S10mini S Hardware Manual

Table of Contents

Advertisement

7 OPERATION PROCEDURES
7.2.3

RUN (ladder program execution) mode

LQP000
CPU RUN
HITACHI
S10mini
7.2.4

SIMU (simulated ladder program execution) mode

LQP000
CPU SIMU
HITACHI
S10mini

7.2.5 RESET mode

LQP000
HITACHI
S10mini
LADDER
RUN
STOP
MODE
SIMU
NORM
PROTECT
OFF
ON
RESET
LADDER
RUN
STOP
MODE
SIMU
NORM
PROTECT
OFF
ON
RESET
LADDER
RUN
STOP
MODE
SIMU
NORM
PROTECT
OFF
ON
RESET
Press
Setting
• Set the CPU operation switch (LADDER)
to RUN.
• Set the mode switch (MODE) to NORM.
CPU status
The user program (ladder) is executed.
Setting
Set the CPU operation switch (LADDER) to
RUN, and also set the mode switch (MODE)
to SIMU.
CPU status
• The user program (ladder) is debugged
with the I/O section stopped.
• User tasks continue their execution.
• Remote I/O transfer stops.
Setting
Hold down the RESET switch for one
second.
Note: Do not press the RESET switch hard.
CPU status
During resetting:
• The indicator displays nothing.
• The program and remote I/O transfer stop.
After resetting:
• The I/O registers (X and Y) and internal
registers (identified by other letters) are
cleared. However, the keep relay (K),
counter (C), or fixed-constant (D) register
is not cleared.
• The CPU starts according to the settings of
the LADDER, MODE, and PROTECT
switches on the CPU module.
- 70 -

Advertisement

Table of Contents
loading

This manual is also suitable for:

S10mini hS10mini fS10mini d

Table of Contents