1 BEFORE USE
Use the programmable controller within the allowable limits of environmental conditions specified
below. Use in a room-temperature, room-humidity environment (15 to 35°C, 45 to 85%RH) is
recommended to assure extended periods of normal operation. Use in a high-temperature, high-
humidity environment where sharp temperature changes are experienced within one day may detract
from the product's useful life.
Supply voltage
Voltage regulation
Temperature
Relative humidity
Resistance to vibration
Resistance to impact
Atmosphere
Even if the input voltage of the power supply module falls within a specified
range, assume it to be in an input power abnormality when it is close to the upper
or lower limit of the range, and call upon the power supply facility manager for a
checkup.
LQV000: 100 to 120 VAC single-phase 50/60 Hz ± 5 Hz
LQV100: 100 to 120 VAC single-phase 50/60 Hz ± 5 Hz
100 to 110 VDC
LQV020: 24 VDC
LQV200: 200 to 240 VAC single-phase 50/60 Hz ± 5 Hz
LQV000: 85 to 132 VAC
LQV100: 85 to 132 VAC
85 to 132 VDC
LQV020: 20.4 to 28.8 VDC
LQV200: 170 to 264 VAC
Operating: 0 to 55°C, Storage: -20 to 75°C
(Rate of temperature change: 10°C/h or lower)
Operating: 30 to 90%RH, Storage: 10 to 90%RH
(Non-condensing)
Compliant with JIS C0040
Frequency: 10 to 150 Hz; Acceleration: 10 m/s
20 sweep cycles in X/Y/Z directions each, 8-minute sweep
Compliant with JIS C0041
Peak acceleration: 147 m/s
Sinusoidal half-wave pulses, three cycles in X, Y, Z directions
each
Dust class: 1 million, no corrosive gases
CAUTION
- 4 -