Processing Time - Hitachi S10mini S Hardware Manual

Table of Contents

Advertisement

8 EXPLANATION OF OPERATION

8.3 Processing Time

Processing time is measured from when an input signal enters the input module until it is output
from the output module. That time is the sum of (1) to (4) shown below.
External
Input module
input signal
Input delay
(1) Input delay
An input delay is taken by the input module to respond. The response time varies with the type
of the input module. For details, refer to the "S10mini HARDWARE MANUAL I/O
MODULE (manual number SME-1-114)."
(2) Remote I/O transfer time
The remote I/O transfer time is taken for data transfer on the remote I/O line. That time varies
with the specified number of I/O points.
512 points: About 5 ms
1024 points: About 10 ms
1536 points: About 16 ms
2048 points: About 21 ms
(3) Ladder processing time
The ladder processing time is taken by the ladder diagram program for processing. That time is
equal to the sequence cycle time (10 to 999 ms).
(4) Output delay
An output delay is taken by the output module to respond. The response time varies with the
type of the output module. For details, refer to the "S10mini HARDWARE MANUAL I/O
MODULE (manual number SME-1-114)."
Calculate the processing time using the following formula:
Processing time = (input delay) + (RI/O transfer time) + (ladder processing time) +
Remote I/O line
CPU module
(
)
(
)
1
2
Transfer
time
processing
(5 to 21 ms)
(10 to 999 ms)
(RI/O transfer time) + (output delay)
Remote I/O line
(
)
(
)
3
2
Ladder
Transfer
time
time
(5 to 21 ms)
- 78 -
Output
module
(
)
4
Output delay
External
output signal

Advertisement

Table of Contents
loading

This manual is also suitable for:

S10mini hS10mini fS10mini d

Table of Contents