Chapter 6 : Installation and Wiring

6.1

Precautions Prior to Installation and Wiring

Due to different installation environments, it is highly recommended that you read this user
manual before installation. Only authorized Delta engineers or service personnel can perform
installation and maintenance. If you want to install the UPS by yourself, installation must be
under the supervision of authorized Delta engineers or service personnel. If you use a forklift
RU RWKHU HTXLSPHQW WR PRYH WKH 836 SOHDVH PDNH VXUH LWV ORDG EHDULQJ LV VXI¿FLHQW )RU WKH
weight of the UPS, please refer to $SSHQGL[   7HFKQLFDO 6SHFL¿FDWLRQV.
6.2

Installation Environment

y
Install the UPS indoors. Do not place it outdoors.
y
Make sure that transportation routes (e.g. corridor, door gate, elevator, etc.) and installation
area can accommodate and bear the weight of the UPS, external battery cabinets, other
equipment that will be installed nearby and forklifts. For the weight of the UPS, please refer
to $SSHQGL[   7HFKQLFDO 6SHFL¿FDWLRQV.
y
The installation place must be kept clean and tidy at all times.
y
Ensure that the installation area is big enough for maintenance and ventilation. Since the
fans of the UPS ventilate from front to rear, and it is recommended that you place the ex-
ternal battery cabinet next to the UPS, we suggest that you:
1. Keep a distance of 100cm from the front of the UPS and the external battery cabinet
for maintenance and ventilation.
2. Keep a distance of 50cm from the back of the UPS and the external battery cabinet for
maintenance and ventilation.
3. Keep a distance of 50cm from the both sides of the UPS and the external battery cabi-
net for maintenance and ventilation.
y
Keep the installation area's temperature around 0°C~40°C and humidity within 95%. The
highest operating altitude is 1000 meters above sea level.
Ultron HPH Integrated Battery Series
WARNING:
Do not use air conditioners or similar equipment to blow into the rear side of the UPS
and hinder ventilation.
26