Chapter 6 : Technical Specifications

Model
Capacity
Voltage Range
Frequency Range
Phase
Power Factor
Nominal voltage
Voltage Regulation
Frequency Range
Frequency Range
(Batt. Mode)
Overload
Current Crest Ratio
Harmonic Distortion
INX-1K
1000 VA / 900 W
Input
Single phase with ground
≥ 0.99 @ nominal voltage (Input Voltage)
Output
200
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
50Hz ± 0.25Hz or 60Hz ± 0.3Hz
100% ~ 110%: Warning only.
110% ~ 130%: The UPS shuts down after 2 minutes in
battery mode or transfer to bypass after 5 minutes when
the utility is normal.
130% ~ 140%: The UPS shuts down after 10 seconds in
battery mode or transfer to bypass after 30 seconds when
the utility is normal.
> 140%: The UPS shuts down after 1.5 seconds or trans-
fer to bypass when the utility is normal.
≤ 2 % THD (linear load); ≤ 4 % THD (non-linear load)
3 0
Chapter 6
INX-2K
2000 VA / 1800 W
1
110-300Vac
40Hz ~ 70Hz
2
2
/208
/220/230/240 Vac
±1% (Batt. Mode)
Ambient Temp.<40°C
3:1
Technical Specifications
INX-3K
3000 VA / 2700 W