Appendix 1 : Technical Specifications - Delta Ultron HPH Series User Manual

Table of Contents

Advertisement

Appendix 1 : Technical Specifications

Model
Power Rating
Waveform
Nominal Voltage
Voltage Range
Frequency
Input
Frequency Range
Input Current
Power Factor
Voltage
Power Factor
Voltage Regulation
Voltage Harmonic
Distortion
Output
Overload Capability
Output Frequency
Cress Factor
Online Mode
Efficiency
ECO Mode
Type
Battery Voltage
Battery
Charge Current
Charge Voltage
Audible Noise
LED & LCD
Appendix 1
HPH-20K
20kVA/20KW
30kVA/30KW
220/380 Vac; 230/400 Vac; 240/415 Vac
300 ~ 477 Vac (100% load)
36.8A
> 0.99 (full load)
220/380 Vac; 230/400 Vac; 340/415 Vac
< 2% (linear load)
≤ 105%: continuous; 106% ~ ≤ 125%: 10 minutes;
126% ~ ≤ 150%: 1 minute; > 150%: 1 second
50/60 Hz ± 0.1 Hz
5A
Float charge 272 ± 2 Vdc
Boost charge 280 ± 2 Vdc
< 55 dBA
LED indicators and Multi-language LCD display
55
Technical Specifications
HPH-30K
HPH-40K
40kVA/40KW
Sine Wave
50/60 Hz
45 ~ 65 Hz
55A
1
± 1%
3:1
Up to 96%
Up to 99%
SMF/ VRLA
± 240 Vdc
5A
< 60 dBA
73A
9A
< 60 dBA

Advertisement

Table of Contents
loading

Table of Contents