Problem
:
Squeegee motor does not run when tested in the Output Test. You will need to determine
if power is getting to the motor.
Possible Cause:
Fuse is blown.
Squeegee linkage is in a bind.
Relay came loose in socket base or has failed.
Motor has failed.
Bad connection to the motor. Check all power wiring to motor.
PLC Output 10CH 07 failed.
Normally this error occurs when Input 1CH 01 fails to receive a signal within 3.5 seconds of
the motor starting. The following list will cover a few things that can cause a SQUEEGEE UP
ERROR.
If the Motor does not run, menu to the INPUT/OUTPUT TEST and press SQUEEGEE LIFT to
check for relay operation and voltages.
Problem
:
The Squeegee motor runs but the up switch failed to operate and send signal to PLC Input
1CH 01.
Possible Cause:
Check and inspect microswitch, manually operate switch to see if Input 1CH 01 will
illuminate.
Possible broken wire or loose connection with either the Yellow (24 VDC) or the
Yellow / Green Wire that connects to Input 1CH 01.
This error can also happen if the squeegee down Input 1CH 00 is stuck on.