Problem
:
Duster Motor UNWIND motor does not run.
Possible Cause
:
 Duster cloth is empty. Replace cloth.
 One or both of the Duster Up Switches are stuck. Check if Input 0CH 10 has an LED
light showing on the PLC with the cushion roller adjusting screws off the switches.
 Duster Unwind Motor has failed.
 Blown fuse.
 Duster Unwind relay failed or is loose in socket base.
 Duster motor wire is damaged or there is a loose wire between the motor and CR4
relay.
 Cleaner dumped onto switch causing it to short, but only a dim light is showing on
Input 0CH 10.
This error screen normally happens when the duster fails to wind-up the cloth and actuate
the duster up switch, failing to turn on Input 0CH 10 on the PLC.
Problem
:
Duster Motor WIND UP motor does not run.
Possible Cause
 Blown fuse.
 Duster Wind-up Motor has failed.
 Duster Up Switches are both broken or out of adjustment.
 Duster Windup relay failed or is loose in socket base.
 Duster cloth cardboard core is loose from the plastic hub.
 Duster hub is slipping on the motor shaft.
 Duster Wind-up Motor wire (Green/Red) is damaged or there is a loose wire between
motor and relay.