so that the air can flow vertically without any obstacles.
• dissipation of device thermal power with effects on installation
room temperature.
• thermal power dissipation with limits on installation room
temperature.
• requires exchange with external air or an air conditioner to
transfer dissipated power outside the panel.
• maximum limits of voltage and derived power of transients on
the line, for which the solid state power unit contains protective
devices (based on the model).
Table 1 EMC Emission
AC semiconductor motor controllers and conductors for
non-motor loads
Emission enclosure
compliant in firing mode single cycle and phase angle if
external filter fitted
Table 2 EMC Immunity
Generic standards, immunity standard for industrial
environments
ESD immunity
RF interference immunity
Conducted disturbance immunity
Burst immunity
Surge immunity
Magnetic fields immunity
Voltage dips, short interruptions and voltage immunity tests
Table 3 LVD safety
Safety requirements for electrical equipment for measurement,
control and laboratory use
ATTENTION
This product has been designed for class A equipment. Use of the product in domestic environments may cause radio
interference, in which case the user may be required to employ additional mitigation methods.
EMC filters are required in PA mode (Phase Angle, i.e., SSR trigger with phase angle modulation).
The filter model and current level depend on the configuration and load used.
The power filter MUST by connected as close as possible to the GFW.
You can use a filter connected between the power line and GFW or an LC group connected between the GFW output and the load
80993B_MHW_GFW-Xtra_06-2018_ENG
• presence of dispersion current in GFW in non-conducting
state (current of a few mA due to RC Snubber circuit to
protect).
GEFRAN S.p.A. assumes no liability for any
damage to persons or property deriving from
tampering, from incorrect or improper use, or
f r o m a n y u s e n o t c o n f o r m i n g t o t h e
characteristics of the controller and to the
instructions in this User Manual.
EN 60947-4-3
EN 60947-4-3
CISPR-11
EN 55011
EN 60947-4-3
EN 61000-4-2
EN 61000-4-3 /A1
EN 61000-4-6
EN 61000-4-4
EN 61000-4-4/5
Test are not required.
Immunity is demonstrated by
the successful completion of
the operating capability test
EN 61000-4-11
EN 61010-1
Class A Group 2
4 kV contact discharge
8 kV air discharge
10 V/m amplitude modulated
80 MHz-1 GHz
10 V/m amplitude modulated
1.4 GHz-2 GHz
10 V/m amplitude modulated
0.15 MHz-80 MHz
2 kV power line
2 kV I/O signal line
Power line-line 1 kV
Power line-earth 2 kV
Signal line-earth 2 kV
Signal line-line 1 kV
100%U, 70%U, 40%U,
5