Port2 (fieldbus): connectors S4, S5 MODBUS RTU/Profibus DP
Figure 30 Port2: Fieldbus Modbus RTU/Profibus DP interface
Table 26
Connector S4
RJ10 4-4 pin
4
3
2
1
Cable type: flat telephone cable for fin 4-4 conductor 28AWG
Table 27
Connector S5
D-SUB 9 pins male
1
2
3
4
5
6
7
8
9
Cable type: Shielded 1 pair 22AWG conforming to PROFIBUS.
80993B_MHW_GFW-Xtra_06-2018_ENG
Nr� Pin
Name
1
GND1 (**)
2
Rx/Tx+
3
Rx/Tx-
4
+V (reserved)
Nr� Pin
Name
1
SHIELD
2
M24V
3
RxD/TxD-P
4
n.c.
5
DGND
6
VP
7
P24V
8
RxD/TxD-N
9
n.c.
Description
-
Data reception/transmission (A+)
Data reception/transmission (B-)
-
Description
EMC protection
Output voltage - 24V
Data reception/transmission
n.c.
Data Ground
Positive power supply +5V
Output voltage +24V
Data reception/transmission
n.c.
S5 female connector
S4 female connector
Yellow Led
Red Led
Green Led
Note
(**) Connect the GND signal
between Modbus devices with a
line distance > 100 m.
Note
Connect the terminal resistances
as shown in the figure.
VP (6)
390 Ω
Data line
RxD/TxD-P (3)
220 Ω
Data line
RxD/TxD-N (8)
390 Ω
DGND (5)