gefran GFW-Xtra 40 Installation And Operation Manual page 37

Modular power controller with overcurrent fault protection
Table of Contents

Advertisement

Figure 48
parameter defines the minimum number of conduction cycles settable from 1 to 10.
In the following example, the parameter = 2.
HSC - Half single cycle
This mode corresponds to Burst Firing that manages ON and OFF half-cycles. It is useful for reducing the
flickering of filaments with short/medium-wave IR lamp loads. With these loads, to limit operating current with
low power, it is useful to set a minimum power limit (for example Lo.P = 10%, ref "GFX4-IR operation guide").
NB.: This mode is NOT allowed with inductive loads (transformers) It is used with resistive loads in single-
phase, star with neutral, or open delta configuration.
Figure 49
Phase angle (PA)
This mode controls power on the load via modulation of trigger angle q
if power to be transferred to the load is 100%, q = 180°
if power to be transferred to the load is 50%, q = 90°
Figure 50
Resistive load
80993B_MHW_GFW-Xtra_06-2018_ENG
Example of operation in HSC mode with power at 33 and 66%.
Inductive load
37