DT -
"Delay triggering" (for ZC, BF control modes only)
Settable from 0° to 90°.
Useful for inductive loads (transformer primaries) to prevent current peak that in certain cases could
trip the high-speed fuses that protect the SCRs.
Figure 53
To conduct inductive loads controlled in PA mode, do not use delay triggering; instead, use the phase Soft-
Start ramp.
Figure 54
Example of phase ramp to fire a
transformer in PA mode
Comparison of method to fire a transformer: Soft-Start Ramp (for PA mode) / Delay triggering (for ZC and BF mode)
80993B_MHW_GFW-Xtra_06-2018_ENG
Transient with
Over-Current
Example of firing of inductive load with/without delay-triggering.
Transient without
Over-Current
Example of firing with Delay-
Triggering of a transformer in ZC
mode