PROFIBUS Power Hub Segment Coupler 3 (SK3)

PROFIBUS Commissioning

5
PROFIBUS Commissioning
5.1

Device Address Assignment

Before mounting the HD2-GTR-4PA gateway module, assign a slave address to the built-in
slave of the gateway.
In order to assign the slave address use the 3 control switches on the motherboard. They can
be used to assign 3–digit addresses.
Permitted Address Ranges
In non-redundant configuration using the motherboard MBHC-FB-4.HSC: 0 ... 125
In redundant configuration using the motherboard MB-FB-GTR1: 500 ... 625
Address setting corresponds to slave address 0, 625 corresponds to slave address 125.
In redundant configuration using the motherboard MB-FB-GTR1: 0 ... 61
Assigning an invalid address for the type of operation required causes the built-in slave to be
deactivated.
In redundant operation, an address must be assigned to the built-in slave.
Assigning the Built-In-Slave (BIS) Address
To assign an address to the built-in slave of the gateway HD2-GTR-4PA, proceed as follows:
1. In order to assign the required 3-digit address of the built-in slaves: Set the control switches
to the correct positions.
2. In order to restart the gateway: Disconnect it from the power supply or unplug the gateway
module and reconnect it. The built-in slave address is assigned.
In the case of redundant coupling, both gateways need to be restarted at the same time.
5.2

Cyclic Data Exchange

A suitable configuration tool is required to configure the cyclic data exchange and to define the
slaves, user data, etc. via a PROFIBUS DP master, class 1.
Commissioning the Simplex and the Redundant System
Note!
No Conversion of the GSD File of the Gateway Module
Because the DP/PA gateway already is a PROFIBUS DP slave, its GSD file does not need to be
converted. The GSD file of the HD2-GTR-4PA is available for download at www.pepperl-
fuchs.com.
In order to start the communication of the HD2-GTR-4PA, proceed as follows:
1. If necessary, convert existing GSD files of PA slaves with the Pepperl+Fuchs
GSD converter. Integrate the converted files into the configuration tool.
2. Integrate the GSD file of the HD2-GTR-4PA in the configuration tool.