Pepperl+Fuchs FieldConnex Segment Coupler 3 Manual page 45

Profibus power hub
Table of Contents

Advertisement

PROFIBUS Power Hub Segment Coupler 3 (SK3)
Operation
Non-redundant masters do not see any effect on PA slaves from redundancy switchover. The
backup gateway takes over communication seamlessly. Both gateways participate in general
token ring operation:
Primary gateway = PA master address 1
Secondary gateway = PA master address 2
Participation in token ring operation thus allows use of handhelds for diagnostic purposes.
Note!
Information: The built-in slave must participate in cyclic data exchange.
In the flying redundancy environment all PA slaves are configured as normal non-redundant
slaves. The built-in slave can be configured as a flying redundancy slave. For additional
information, see chapter 8.
Master 1
Applications with Redundant Operation
Redundancy is available in the following cases:
Both gateways are in operation with no errors
Both gateways detect DP baud rates
No errors occurred in PA communication
If redundant operation is not available, this is reported back by the slave diagnostics.
Possible reasons for redundancy switchover are the following:
Hardware error in the primary gateway
Loss of baud rate (cable break, etc.)
Built-in slave drops out of the cycle (because of an unlock from the master or the
watchdog time has expired, etc.)
Redundancy switching in either of the following cases:
Both built-in slaves dropped out of communication and the primary BIS immediately
comes up on the bus again
The built-in slaves on the DP bus have changed roles
The primary gateway can be identified by the following LED: "Red." (redundancy) is flashing or
lights up.
Master 2*
Primary
PA Slave
Gateway
PA Slave
PA Slave
Backup
PA Slave
Gateway
*Flying Redundancy
45

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sk3Fieldconnex hd2-gtr-4pa

Table of Contents