PROFIBUS Power Hub Segment Coupler 3 (SK3)

Troubleshooting

11
Troubleshooting
This chapter helps you to solve problems that may occur in connections with commissioning or
operating your Power Hub.
Note!
First Checks in Case of Problems
In case a fault occurs, first ensure that the field wiring is complete, properly terminated, and that
all field spurs are properly attached. Also check if the gateway module(s) and the power
modules are properly plugged into the connection slots of the respective motherboards.
11.1

Faults Indicated via LEDs

Symptom
LED "PWR" is off
LED "DP/ERR" is flashing red
LED "DP/ERR" lights up
constantly red
LED "Red." (Redundancy) is
flashing yellow
LED "Red." is off
Possible cause
No power.
Gateway defective.
No data transmission on
DP side.
Master problem.
Gateway defective.
Hardware error.
Redundancy not available. 
Reasons:
Synchronization in
progress.
Second gateway module is
missing on a redundant
board.
Backup gateway is
defective.
Gateway module is
plugged into simplex
motherboard.
Only 1 gateway module is
plugged into redundant
motherboard.
Redundant board is used
and LED "Red." lights up
constantly yellow at
primary gateway.
Remedy
Check power supply.
Restart gateway.
If problem persists, send
gateway to Pepperl+Fuchs.
Check cables.
Check termination.
Check master.
Restart gateway.
If problem persists, send
gateway to Pepperl+Fuchs.
Restart gateway.
If problem persists, send
gateway to Pepperl+Fuchs.
Not a fault. Wait a few
seconds.
Plug in second gateway
module.
Send gateway to Pepperl+
Fuchs.
If problem persists, send
gateway to Pepperl+Fuchs.
Use redundant
motherboard.
Not a fault.
Not a fault. Gateway is
backup device.