PROFIBUS Power Hub Segment Coupler 3 (SK3)
Troubleshooting
Symptom
PA bus master parameters
(WD mode, WD time, no. of
retries, segment no.) cannot
be written.
Diagnostic module error or
module missing.
ADM reports system
maintenance required.
ADM reports system out of
specification.
ADM reports segment
maintenance required.
ADM reports segment out of
specification.
11.3
Fault Indicated via DCS
Note!
First Checks concerning the DCS
In case faults are indicated via the control system, make sure the built- in slaves of your
PROFIBUS Power Hub system are correctly integrated into the engineering tool.
Symptom
PA slaves keep leaving cyclic
data exchange.
PA slaves and DP slaves keep
leaving cyclic data exchange.
Device diagnostics: No
redundancy even though
2 gateway modules are used.
Device diagnostics:
"Redundancy partner
missing"
Possible cause
PA bus master parameters are
write-protected. Reason: Built-
in slave is in cyclic data
exchange using PA bus
configuration module.
Diagnostic module is defect or
was removed (by active ADM
alarm observer only).
At least one monitored system
value has violated the preset
limit.
Possible cause
Termination problem on
■
PA side
Fault on PA bus
■
Poor signal quality on
■
PA side
Watchdog time too short
■
Fault on DP bus
■
Poor signal quality on
■
DP side
Poor signal quality
■
Gateway module is
■
defective
No second gateway
■
module plugged into
motherboard
Secondary gateway
■
module has failed
Remedy
Use different module to
configure cyclic data
exchange.
Replace diagnostic
■
module
Switch off ADM alarm
■
observer
Perform diagnostics with the
DTM diagnostic manager for
detailed information.
For further information see the
documentation on the
"Advanced Diagnostic Module
HD2-DM-A".
Remedy
Check termination
■
Eliminate fault on PA bus
■
Perform physical layer
■
diagnostics on PA side
with advanced diagnostic
module
Increase watchdog time
■
Eliminate fault on DP bus
■
Check DP signal quality
■
Perform physical layer
■
diagnostics on the PA side
with the advanced
diagnostic module.
Send gateway to Pepperl+
■
Fuchs.
Plug second gateway
■
module into motherboard
Replace second gateway
■
module
61