Retry Limits; Device Type Manager (Dtm): Installation And Commissioning - Pepperl+Fuchs FieldConnex Segment Coupler 3 Manual

Profibus power hub
Table of Contents

Advertisement

PROFIBUS Power Hub Segment Coupler 3 (SK3)
PROFIBUS Commissioning
Note!
Cycle Time Discrepancy in Realworld Applications
This is the basic cycle time under ideal conditions. In reality, acyclic communication, retries,
and diagnostic data can increase the cycle time, requiring an additional safety margin to be
added.
For the calculation of an overall cycle time (change of a measured signal until reaction of an
actuator), additional parameters like the measurement cycle time of the PROFIBUS PA devices
and IO processing cycle of the controller must be considered.
5.2.4

Retry Limits

Adjusting the Retry Limit for Fiberoptical Communication
If the coupling from PROFIBUS DP to PA is designed redundantly and the DP bus uses optical
fiber as a communication medium, Pepperl+Fuchs recommends increasing the retry limit of the
DP master.
Recommended retry limits corresponding to various baud rates:
Baud Rate
45.45 kBd
93.75 kBd
187.5 kBd
1.5 kBd
3 kBd
6 kBd
12 kBd
5.2.5

Device Type Manager (DTM): Installation and Commissioning

System requirements for installation, commissioning, and operation of the DP/PA gateway
device type manager (DTM):
Hardware requirements based on your FDT frame application
FDT frame application (FDT specification 1.2)
Latest version of the HD2-GTR-4PA DTM
40 MB free hard drive storage
Installing the DTM Package with PACTware
In order to install the DTM package on your system, proceed as follows:
1. Install the P+F-FieldConnex
2. Start the PACTware
3. Update the device catalog.
Retry Limit
2
2
2
2
4
6
7
DTM package.
®
TM
program.
TM
(Example)
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sk3Fieldconnex hd2-gtr-4pa

Table of Contents