Pepperl+Fuchs FieldConnex Segment Coupler 3 Manual page 16

Profibus power hub
Table of Contents

Advertisement

PROFIBUS Power Hub Segment Coupler 3 (SK3)
Product Specifications
System Overview
Standard conformity
Electrical isolation
Electromagnetic compatibility
Degree of protection
Fieldbus standard
Shock resistance
Vibration resistance
HD2-GTR-4PA
System Overview
Supply
Rated voltage
Rated current
Power dissipation
Fieldbus interface
PROFIBUS DP
Connection
Protocol
Electrical isolation
CH/PROFIBUS DP
PROFIBUS DP/Supply
CH/CH
All circuits/FE
Data for application in connection with Ex-areas
Statement of conformity
Group, category, type of
protection, temperature class
Directive conformity
Directive 94/9/EC
International approvals
FM approval
Approved for
IECEx approval
Approved for
MB-FB-GTR1*
Supply
Rated voltage
Rated current
Indicators/operating means
16
IEC 62103
NE 21:2011
IEC 60529
IEC 61158-2
EN 60068-2-27
EN 60068-2-6
19.2 ... 35 V DC
160 ... 90 mA
3 W
9-pin Sub-D socket
PROFIBUS DP V1
functional insulation acc. to IEC 62103, rated insulation
voltage 50 V
eff
TÜV 04 ATEX 2500 X
II 3 G Ex nA IIC T4 Gc
EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-
15:2010
CoC 3024816, CoC 3024816C
Class I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2,
AEx/Ex nA IIC T4
IECEx TUN 13.0038X
Ex nA IIC T4 Gc
19.2 ... 35 V SELV/PELV
2 ... 3 A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sk3Fieldconnex hd2-gtr-4pa

Table of Contents