Setting The Functional Parameters - Riello ALU PRO power Series Instructions For The Installer And The Technical Assistance Centre

Aluminium condensing boilers
Table of Contents

Advertisement

If an outdoor temperature sensor is connected, the controller uses the heating curve to generate the CH flow tempera-
ture setpoint, thus enabling the boiler to maintain a constant room temperature even without the use of an ambient unit
.The steeper the slope of the heating curve, the higher the flow temperature setpoint at low outdoor temperatures (see
"Installer" parameter 532).
Heating curves with room temperature setpoint = 15°C
S=3,5 S=4 S=4,5 S=5
100
S=3
S=2,5
90
80
S=2
70
S=1,5
60
50
S=1
40
S=0,5
30
20
S=0
15
10
S = Pendenza Curva
S = Curve Slope
0
-10
-20
-15
Heating curves with room temperature setpoint = 20°C
100
S=2,5
90
S=2
80
S=1,5
70
60
S=1
50
S=0,5
40
30
S=0
20
S = Pendenza Curva
S = Curve Slope
10
0
-10
-20
-15
100
90
80
70
60
50
40
30
-10
-5
0
5
Temperatura Esterna (°C)
Outdoor Temperature (°C)
S=3
S=3,5
S=4 S=4,5
100
90
80
70
60
50
40
30
-10
-5
0
5
Temperatura Esterna (°C)
Outdoor Temperature (°C)

SETTING THE FUNCTIONAL PARAMETERS

10
15
20
S=5
10
15
20
TECHNICAL ASSISTANCE CENTRE
25
30
35
40
25
30
35
40
57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents