Riello ALU PRO power Series Instructions For The Installer And The Technical Assistance Centre page 64

Aluminium condensing boilers
Table of Contents

Advertisement

OEM Menu
To access the OEM menu press the "up arrow and down arrow" keys at the same time for eight seconds; you access
the page for entering the password composed of the following sequence of keys: "down arrow" , "up arrow" , "+" , "-",
"+". If the password is incorrect you return to the installer menu; if it is correct you enter the OEM menu, and in the top
right (small digits) the number of the selected parameter will appear and in the middle (large digits) the value it has.
To move forward through the parameters press the "up arrow" or "down arrow" keys and to change the value of the
parameter press the "+" or "–" keys.
To exit the menu press the "i" or "mode" keys.
Code
Description
C513
Storage cylinder maximum temperature
C515
Limit temperature for switching off the boiler
C517
Maximum delivery temperature of the modules
C518
Safety temperature
C559
Domestic hot water request mode
C592
Flue gases temperature for boiler shut-down
C593
Flue gas temperature for reducing heat output
C604
Strategy selection for igniting modules
C607
Period for sending output setpoint to the modules
Maximum variation of the output setpoint to be
C608
sent to the modules
C609
Threshold for switching on module in strategy B
C612
Threshold for switching off module in strategy B
C613
Protection activation mode with fuel valve
Delta temperature for the simultaneous ignition of
C616
all the modules in strategy B
Operating time for rotation of modules in strategy
C618
B (in 1h)
C700
PID adjustment for CH – Kp
C701
PID adjustment for CH – Ti
C702
PID adjustment for CH – Ki
C703
PID adjustment for DHW – Kp
C704
PID adjustment for DHW – Ti
C705
PID adjustment for DHW – Ki
C706
PID adjustment for modulating pump – Kp
C707
PID adjustment for modulating pump – Ti
C708
PID adjustment for modulating pump – Ki
C750
operating mode 0-10V device
Number of SIC712 modules that need to be con-
C800
nected to the system
C801
Enabling saturation management of modules
Threshold for recognition of modules saturation
C802
condition
C803
Threshold for exiting modules saturation condition
C804
Standby time for modules saturation status
(*) - Number of modules in the boiler.
64
TECHNICAL ASSISTANCE CENTRE
Minimum
Maximum
50°C
80°C
85°C
100°C
80°C
95°C
90°C
110°C
0
85°C
120°C
80°C
115°C
0
10s
255s
4%
99%
C612 x 2
99%
1%
C609 / 2
0
1°C
50°C
10h
127h
0
0
0
0
0
0
0
0
0
0
0
0
C803
100%
0%
C802
0sec
240sec
Default
70°C
95°C
90°C
99°C
2
1
90°C
85°C
1
0
20s
6%
50%
4%
1
0
30°C
100h
99
5
99
50
99
1
99
1
99
5
99
1
99
5
99
11
99
1
2
0
(*)
8
1
1
12%
3%
15sec

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents