Riello ALU PRO power Series Instructions For The Installer And The Technical Assistance Centre page 43

Aluminium condensing boilers
Table of Contents

Advertisement

Collegare solo pompe
Connect only pumps with a
con un assorbimento
maximum energy absorption
elettrico massimo
equal to or less than 1A
inferiore o uguale a 1A
Central heating
Pompa Impianto
pump
Storage cylinder
Pompa Bollitore
pump
Valvola
intercettazione
Fuel check valve
combustibile
MAX 3A
MAX 3A
250Vac
250Vac
cos
cos =1
Sonda bollitore
Storage tank probe
Sonda esterna
Outdoor probe
Ingresso 0-10V
0-10V input
0-10V outlet for heating system pump
Uscita 0-10V per pompa impianto
0-10V
SB
SE
0-10V
in
in
- Once you have made all the necessary connections, close the control panel, reversing the steps followed to open it.
b
If there is a storage cylinder, the cylinder probe must be placed following the instructions of the cylinder itself.
b
For information on how to connect up additional kits, refer to the instructions provided with the kits themselves.
5
12
N
L1
N
L1
N
L1
Storage tank probe
Sonda bollitore
Outdoor probe
Sonda esterna
Ingresso 0-10V
0-10V input
uscita 0-10V
0-10V output
=1
Contatto
Alarm
Allarme
contact
NA
C
0-10V
0-10V
out
out
Central heating pump
Pompa Impianto
Storage cylinder pump
Pompa Bollitore
Gas valve
Valvola gas
Alarm contact
Contatto allarme
Alimentazione elettrica
Electrical supply
Electrical supply
Alimentazione elettrica
L
N PE
6
13
Room thermostat
Termostato ambiente
Open-Term
Open-Term
Termostato
Room
ambiente
thermostat
Open-Term
Open-Term
OT
OT
TA TA
Stringere
Properly tighten the
adeguatamente
fair leads
i pressacavi
Utilizzare cavi con
Use cables with a section
sezione maggiore o
greater than or equal to
2
uguale a 1,5 mm
,
1.5mm2, complete with
completi di puntalini
cable terminal caps.
capocorda.
INSTALLER
43