Adjusting the gas pressure switch
To ensure the boiler operates correctly, adjust the mini-
mum gas pressure switch to a value of at least 5 to 10
mbar below that of the gas supply pressure.
To do this:
- Remove the screws securing the pressure switch cover
(5)
- Adjust the knob (6) to the desired value
- Put back the cover and secure it with the screws
removed previously.
- Apply the label (7) for G31, supplied with the kit, inside the panelling, and remove the one for G20
- Remove the gas label (8) from the outside.
7
56
TECHNICAL ASSISTANCE CENTRE
5
6
Paese di destinazione:
Tipo di apparecchio
:
B23P
II
Caldaia categoria
:
2H3P
Pressioni di alimentazione gas:
G20
20 mbar
G31
37 mbar
Regolazione effettuata dal costruttore:
G20 - 20 mbar