NOTE
• The number of readout digits of the cumulative energization time (Pr.52 = "20"), actual operation time (Pr.52 = "23"),
cumulative energy (Pr.52 = "25"), and cumulative energy saving (Pr.52 = "51") does not change.
 Enabling display of negative numbers during monitoring (Pr.290)
• Negative values can be used for indication via terminal AM (analog voltage output), on communication options, and via
terminal AM0 (of the FR-A8AY). To check which items can be monitored with indication of negative numbers, refer to
Monitor description list (on
Pr.290 setting
0 (initial value)
1
4
5
8
9
12
13
—: Negative numbers indication disabled (positive only)
*1
Negative numbers indication is disabled via RS-485 communication (Mitsubishi inverter protocol or MODBUS RTU).
NOTE
• When indication with negative numbers is enabled for the output via terminal AM/AM0 (analog voltage output), the output is
within the range of -10 to +10 VDC. Connect the meter with which output level is matched.
• The operation panel displays only unsigned numbers.
 Monitor filter (Pr.1106 to Pr.1108)
• The response level (filter time constant) of the following monitor indicators can be adjusted. Increase the setting when a
monitor indicator is unstable, for example.
Pr.
Monitor number
7
17
1106
32
33
1107
6
1108
18
Parameters referred to
Pr.53 Frequency / rotation speed unit
Pr.55 Frequency monitoring reference, Pr.56 Current monitoring reference, Pr.866 Torque monitoring
278
12. (M) Item and Output Signal for Monitoring
12.2 Monitor item selection on operation panel or via communication
page
271).
Negative numbers
indication (via terminal AM)
Enabled
Enabled
Enabled
Enabled
Monitor indicator name
Motor torque
Load meter
Torque command
Torque current command
Motor speed
Motor excitation current
switchoverpage 268
Negative numbers
indication (via
*1
communication option)
Enabled
Enabled
Enabled
Enabled
Negative numbers indication (via
terminal AM0) (with the FR-A8AY)
Enabled
Enabled
Enabled
Enabled
referencepage 279