Mitsubishi Electric FR-E800 Series Instruction Manual page 433

Compact, high functionality inverters
Hide thumbs Also See for FR-E800 Series:
Table of Contents

Advertisement

16.4
Energy saving control
V/F
V/F
V/F
The inverter will automatically perform energy saving operation without setting detailed parameters.
This control method is suitable for applications such as fans and pumps.
Pr.
60
Energy saving
G030
control selection
 Optimum excitation control (Pr.60 = "9")
• Setting Pr.60 = "9" will select the Optimum excitation control.
• The Optimum excitation control is a control method to decide the output voltage by controlling the excitation current so the
efficiency of the motor is maximized.
• Energy saving operation will be enabled under V/F control.
NOTE
• In the Optimum excitation control mode, an energy saving effect is not expected when the motor capacity is extremely small
compared with the inverter capacity or when multiple motors are connected to a single inverter.
• When the Optimum excitation control mode is selected, the deceleration time may become longer than the setting value. Also,
it may cause overvoltage more often compared to constant-torque load characteristics, so set the deceleration time longer.
• When the motor becomes unstable during the acceleration, set the acceleration time longer.
• Output current may increase slightly with the energy saving operation mode or the Optimum excitation control mode since the
output voltage is controlled.
432
16. (G) Control Parameters
16.4 Energy saving control
Name
Initial value
0
Setting range
0
Normal operation
9
Optimum excitation control
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents