Password - Mitsubishi Electric FR-E800 Series Instruction Manual

Compact, high functionality inverters
Hide thumbs Also See for FR-E800 Series:
Table of Contents

Advertisement

8.11

Password

Registering a 4-digit password can restrict access to parameters (reading/writing).
Pr.
Name
296
Password lock level
E410
297
Password lock/unlock
E411
These parameters can be set when Pr.160 User group read selection = "0". However, when Pr.296 ≠ 9999 (password lock
is set), Pr.297 can always be set, regardless of the setting in Pr.160.
*1
Although "0 or 9999" can be input in Pr.297, the value is invalid. (The display cannot be changed.)
 Parameter reading/writing restriction level (Pr.296)
• The access (reading/writing) restriction level to parameters in the PU operation mode or NET operation mode can be
selected with Pr.296.
PU operation mode operation
Pr.296 setting
Read
9999
*6
×
0, 100
1, 101
2, 102
3, 103
4, 104
×
5, 105
×
6, 106
Only the parameters registered in the user group can be read/written. (For the parameters not registered in the user
99, 199
group, the restriction level when "4 or 104" is set applies.)
○: Enabled, ×: Disabled
*1
If the parameter reading is restricted by the setting of Pr.160 User group read selection, those parameters cannot be read even when "○" is
indicated.
*2
If the parameter writing is restricted by the setting of Pr.77 Parameter write selection, those parameters cannot be written even when "○" is
indicated.
*3
Access from the command source in the PU operation mode (the operation panel in the initial setting) is restricted. (For the PU operation mode
command source selection, refer to
*4
Access from the command source in the Network operation mode (the RS-485 communication or a communication option in the initial setting) is
restricted. (For the NET operation mode command source selection, refer to
*5
Read/write is enabled only for the simple mode parameters registered in the user group when Pr.160 = "9999". Pr.296 and Pr.297 are always
read/write enabled whether registered to a user group or not.
*6
If a communication option is installed, the Option fault (E.OPT) occurs, and the inverter output shuts off.
*7
The PLC function user parameters (Pr.1150 to Pr.1199) can be written and read by the PLC function regardless of the Pr.296 setting.
 Locking parameters with a password (Pr.296, Pr.297)
• The procedure of locking parameters with a password is as follows.
1.
Set the parameter reading/writing restriction level to enable the password protection. (Set a value other than "9999"
in Pr.296.)
Allowable number of failed password
Pr.296 setting
0 to 6, or 99
Unlimited
*1
Limited to 5 times
100 to 106, 199
Initial value
9999
9999
*3
command
*1
*2
Write
×
×
×
×
×
×
×
×
page
223.)
attempts
Setting range
Password protection enabled. Setting the access
0 to 6, 99, 100 to
(reading/writing) restriction level to parameters locked
106, 199
with a password enables writing to Pr.297.
9999
No password protection
Input a 4-digit password to lock parameters, or input the
1000 to 9998
valid password to unlock the locked parameters.
Number of failed password attempts (read only,
*1
displayed after any of "100 to 106, or 199" is set in
(0 to 5)
Pr.296 and a password to lock parameters is input).
*1
No password protection
9999
NET operation mode operation command
RS-485 communication / PLC
*7
function
*2
Read
Write
×
×
×
×
×
*5
page
223.)
Pr.297 readout
Always 0
Number of failed password attempts (0 to 5)
Description
*4
via communication option
Read
Write
×
×
×
×
×
×
8. (E) Environment Setting Parameters
8.11 Password
1
2
3
4
5
6
7
8
*2
9
10
175

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents