The degree of deterioration of the control circuit capacitor, main circuit capacitor, cooling fan, and inrush current limit circuit can
be diagnosed on the monitor. When a part approaches the end of its life, an alarm can be output by self diagnosis to prevent
a fault. (Note that the life diagnosis of this function should be used as a guideline only, the life values are theoretical
calculations.)
Pr.
198
Display corrosion level
E709
255
Life alarm status display
E700
256
Inrush current limit circuit life
E701
display
257
Control circuit capacitor life
E702
display
258
Main circuit capacitor life display 100%
E703
259
Main circuit capacitor life
E704
measuring
506
Display estimated main circuit
E705
capacitor residual life
507
Display ABC relay contact life
E706
509
Display power cycle life
E708
 Life alarm display and signal output (Y90 signal, Pr.255)
• In the life diagnosis of the main circuit capacitor, the Life alarm (Y90) signal is not output unless measurement by turning OFF
the power supply is performed.
• Pr.255 Life alarm status display and the Life alarm (Y90) signal can be used to check whether or not the life alarm output
level is reached for the following parts: the control circuit capacitor, main circuit capacitor, cooling fan, inrush current limit
circuit, relay contacts of terminals A, B, and C, inverter module, or control circuit board.
bit
15
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1
bit8 Life of the inverter module
bit9 Corrosion level
186
8. (E) Environment Setting Parameters
8.16 Inverter parts life display
Name
Initial value
1
0
100%
100%
0
100%
100%
100%
7
0
bit0 Control circuit capacitor life
bit1 Main circuit capacitor life
bit2 Cooling fan life
bit3 Inrush current limit circuit life
bit5 Estimated residual-life of main circuit capacitor
bit6 Life of relay contacts of terminals A, B, and C
Setting range
Displays the corrosion level of the control circuit board.
1 to 3
Read-only. (Available only for the FR-E8[][]-[]-60 (with
coating).)
Displays whether or not the life alarm output level is
reached for the following parts: the control circuit
capacitor, main circuit capacitor, cooling fan, inrush
(0 to 879)
current limit circuit, relay contacts of terminals A, B, and
C, inverter module, and control circuit board. Read-
only.
Displays the deterioration degree of the inrush current
(0% to 100%)
limit circuit. Read-only.
Displays the deterioration degree of the control circuit
(0% to 100%)
capacitor. Read-only.
Displays the deterioration degree of the main circuit
capacitor. Read-only.
(0% to 100%)
The value measured by Pr.259 is displayed.
Setting "1" and turning the power supply OFF starts the
measurement of the main circuit capacitor life.
If the setting value of Pr.259 becomes "3" after turning
0, 1, (2, 3, 8, 9)
the power supply ON again, it means that the
measurement is completed. The deterioration degree is
read to Pr.258.
Displays the estimated residual life of the main circuit
(0% to 100%)
capacitor. Read-only.
Displays the degree of deterioration of the relay
0% to 100%
contacts of terminals A, B, and C.
Displays the degree of deterioration of the inverter
(0% to 100%)
module. Read-only.
• Pr.255 read
Description
• Pr.255 setting read
Bit image is displayed
in decimal