Mitsubishi Electric FR-E800 Series Instruction Manual page 297

Compact, high functionality inverters
Hide thumbs Also See for FR-E800 Series:
Table of Contents

Advertisement

*1
Note that changing the frequency setting with an analog signal or the setting dial on the operation panel may cause the turning ON and OFF of
Up to frequency (SU) signal depending on its changing speed and the timing of the speed change determined by the acceleration/deceleration
time setting. (The signal state changing does not occur when the acceleration/deceleration time is set to 0 second.)
*2
Available when the plug-in option is connected.
NOTE
• One function can be assigned to more than one terminal.
• The function works during the terminal conducts when the parameter setting is any of "0 to 99, 200 to 299", and the function
works during the terminal does not conduct when the setting is "100 to 199, 300 to 399".
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
• Do not assign the signal to terminals A, B, and C which frequently changes its state between ON and OFF. Otherwise, the life
of the relay contact may be shortened.
 Adjusting the output terminal response level (Pr.289)
• The responsivity of the output terminals can be delayed in a range between 5 to 50 ms. (The following is the operation
example of the RUN signal.)
RUN
Pr.289 = 9999
RUN
Pr.289 ≠ 9999
NOTE
• When Pr.157 OL signal output timer is set for the Overload warning (OL) signal output, the OL signal is output after the time
period calculated by adding the Pr.289 setting to the Pr.157 setting elapsed.
• The signal output for the PLC function (see
by the Pr.289 setting (not filtered for responsivity).
 Inverter operation ready signals (RY, RY2 signals) and inverter running
signals (RUN, RUN2, RUN3 signals)
• When the inverter is ready for operation, the Inverter operation ready (RY) signal turns ON (and stays ON during
operation).
• When the inverter output frequency reaches the setting of Pr.13 Starting frequency or higher, the inverter running signals
(RUN, RUN2 signals) turn ON. The signals are OFF while the inverter is stopped or during the DC injection brake operation.
296
12. (M) Item and Output Signal for Monitoring
12.6 Output terminal function selection
OFF
ON
ON
Pr.289
Pr.289
page
Time
OFF
416) and the remote output signal via BACnet communication are not affected