Mitsubishi Electric FR-E800 Series Instruction Manual page 283

Compact, high functionality inverters
Hide thumbs Also See for FR-E800 Series:
Table of Contents

Advertisement

FM output circuit
Inverter
24V
2.2K
3.3K
FM
20K
SD
FM
Calibration
resistor
SD
Pulse width T1: Adjust using calibration parameter C0
Pulse cycle T2: Set with Pr.55 (frequency monitor)
*1
Not required when calibrating with operation panel.
Use a calibration resistor when the indicator (frequency meter) needs to be calibrated by a neighboring device because the indicator is located
far from the inverter.
However, the frequency meter needle may not deflect to full-scale if the calibration resistor is connected. In this case, use the resistor and
operation panel together.
*2
In the initial setting, 1 mA full-scale and 1440 pulses/s terminal FM are used at 60 Hz.
282
12. (M) Item and Output Signal for Monitoring
12.3 Monitor display selection for terminals FM and AM
Indicator
1mA full-scale
analog meter
1mA
(+)
(-)
*1
8VDC
Set with Pr.56 (current monitor)
FM
T1
SD
T2
(Digital indicator)
(-)
1440 pulses/s(+)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents