 Changing the motor constants (when setting motor constants in the
internal data of the inverter)
• Set Pr.71 as follows.
• 200/400 V class
Mitsubishi Electric high-performance energy-saving
motor
Mitsubishi Electric high-performance energy-saving
motor with encoder
Mitsubishi Electric Vector control dedicated motor
Mitsubishi Electric geared motor
Mitsubishi Electric inverter-driven geared motor for
encoder feedback control
Mitsubishi Electric standard efficiency motor
Mitsubishi Electric high-efficiency motor
Mitsubishi Electric constant-torque motor
Other manufacturer's standard motor
Other manufacturer's constant-torque motor
• 575 V class
Vector control dedicated motor
Standard motor
Constant-torque motor
Other manufacturer's standard motor
Other manufacturer's constant-torque motor
• Set desired values as the motor constant parameters.
First
Second
motor Pr.
motor Pr.
82
455
90
458
91
459
92
460
93
461
94
462
859
860
298
560
717
741
720
737
NOTE
• As the motor constants measured in the offline auto tuning have been converted into internal data (****), refer to the following
setting example when making setting. (The value displayed has been converted into a value for internal use. Therefore, simple
addition of a value to the displayed value does not bring the desired effect.)
Setting example: To slightly increase the Pr.90 value (5%)
When "2516" is displayed for Pr.90, set 2642 (2516 × 1.05 = 2641.8) in Pr.90.
• If "9999" is set in the motor constant parameters, tuning data will be invalid and the constant values for Mitsubishi Electric
motors (SF-PR, SF-PR-SC, SF-JR, SF-HR, SF-JRCA, SF-HRCA, SF-V5RU (1500 r/min series), GM-[], GM-DZ, or GM-DP)
are used.
352
14. (C) Motor Constant Parameters
14.2 Offline auto tuning
Motor
SF-PR
SF-PR-SC
SF-V5RU (1500 r/min series)
GM-[]
GM-DZ, GM-DP
SF-JR
SF-JR 4P 1.5 kW or lower
SF-HR
Others
SF-JRCA 4P
SF-HRCA
Other (SF-JRC, etc.)
Motor
Name
Motor excitation current
Motor constant (R1)
Motor constant (R2)
Motor constant (L1)/d-axis inductance (Ld)
Motor constant (L2)/q-axis inductance (Lq)
Motor constant (X)
Torque current/Rated PM motor current
Frequency search gain
Starting resistance tuning compensation coefficient 1
Starting resistance tuning compensation coefficient 2
Pr.71 setting
73
33
1803
3
23
43
3
13
53
13
3
13
Pr.71 setting
33
3
13
3
13
Setting
Setting range
increments
0 to ***, 9999
1
0 to 32767, 9999
1
0% to 200%
0.1%
0% to 200%
0.1%
Initial
value
9999