• When Pr.414 = "2 or 12", the SQ signal can be input only via an external input terminal regardless of the Pr.338 setting.
• The following shows the required conditions to enable the SQ signal.
Pr.414 setting
Pr.338 setting
0
1, 11
1
2, 12
—: Not required to enable the SQ signal
 User parameter (data register (D)) auto storage function selection
• Setting Pr.675 = "1" enables the auto storage function for user parameters.
• The user parameter auto storage function is used to store the setting of Pr.1195 PLC function user parameters 46 (D251)
to Pr.1199 PLC function user parameters 50 (D255) automatically in EEPROM at power OFF or inverter reset.
• The auto storage function is disabled while the inverter performs any of the following.
Measurement of the main circuit capacitor's life, offline auto tuning, or measurement of load characteristics
NOTE
• The auto storage function may fail if the EEPROM is accessed by other functions at the same time at power OFF. To ensure
the auto storage, provide a power source for the control circuit separately from that of the main circuit.
 User parameter reading from EEPROM
• User parameters (Pr.1150 to Pr.1199) are read from RAM or EEPROM according to the settings in Pr.342
Communication EEPROM write selection and Pr.414 PLC function operation selection. When Pr.414 = "11 or 12",
RAM data is read regardless of the Pr.342 setting.
Device
Inverter (via communication),
FR Configurator2
Communication option
Operation panel
NOTE
• For the details of the PLC function, refer to the PLC Function Programming Manual and the Instruction Manual of FR
Configurator2.
Input via an external (physical) terminal
ON
ON
ON
Pr.342
Pr.414
0, 1, 2
EEPROM
0
11, 12
RAM
0, 1, 2
RAM
1
11, 12
RAM
0, 1, 2
(Differs according to the option type.)
0
11, 12
RAM
0, 1, 2
RAM
1
11, 12
RAM
0, 1, 2
EEPROM
0
11, 12
RAM
0, 1, 2
EEPROM
1
11, 12
RAM
SQ signal
Input via a communication virtual terminal
ON
ON (terminal NET X)
Read from
EEPROM
RAM
EEPROM
RAM
EEPROM
RAM
15. (A) Application Parameters
11
12
13
14
15
16
17
18
Written to
19
20
417
15.11 PLC function