Configuring and commissioning using ETS

8.3 Programming the physical address

8.3
Programming the physical address
Set the device to programming mode using the key on the front of the CMK2000. In this
programming mode it is possible to assign (program) the address to the CMK2000 using the
ETS. The physical address (1.0.1 to 15.15.254) unambiguously identifies a KNX in a KNX
installation. The physical address is assigned using the topology configured in ETS.
Requirements
● PC with ETS is connected to the KNX installation via a KNX interface
● CMK2000 is connected to KNX
Programming the physical address
1. Set CMK2000 to programming mode:
Briefly press the key on the front of the CMK2000 (< 10 seconds).
Note
You can deactivate programming mode by briefly pressing the key again.
2. Program the physical address by selecting the device in ETS and then "Programming" →
"Physical address".
Note
• Parameter assignments can only be transferred to the device following successful
• If an error occurs when programming the physical address, the CMK2000 remains in
• The physical address must be programmed once so that the device with the ETS is
3. Label the CMK2000 with the assigned physical address in the labeling field (Page 21)
provided for this purpose.
40
NOTICE
Programming mode must not be activated when updating the firmware using the web
interface.
setting of the physical address.
programming mode. However, if the 24 V supply fails during programming of the
physical address, the CMK2000 is no longer in programming mode following a hot
restart.
always accessible. The physical address is saved in the CMK2000 and automatically
set again in the CMK2000 following a restart.
Operating Instructions, 11/2015, A5E34877550B/001