  • Page 3 ___________________ CMK2000 Introduction ___________________ Safety notes ___________________ LOGO! System overview ___________________ Application planning CMK2000 ___________________ Installing/mounting ___________________ Connection Operating Instructions ___________________ Generation of user functions with LOGO! ___________________ Configuring and commissioning using ETS ___________________ Service and maintenance ___________________ Technical data ___________________ Appendix 11/2015...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Table of contents Introduction ............................. 9 Preface ............................9 Safety notes ............................11 Safety instructions ........................11 IT security ..........................13 System overview ........................... 15 Field of application ........................15 Features ..........................16 System configuration ......................17 System requirements ......................18 Design .............................
  • Page 6 Table of contents Configuring and commissioning using ETS ................... 39 Software and hardware requirements (ETS) ................. 39 Overview of ETS configuration steps ..................39 Programming the physical address..................40 General parameter assignments.................... 41 Parameter assignments for the KNX channels ..............44 8.5.1 Data exchange between KNX and LOGO! ................
  • Page 7 Appendix............................... 85 Certificates and approvals ...................... 85 Service & Support ........................86 A.2.1 Technical Support ........................86 A.2.2 Siemens Industry Online Support ................... 86 A.2.3 Online catalog and ordering system ..................86 A.2.4 LOGO! CMK2000 ........................86 Glossary ............................... 87 Index..............................
  • Page 8 Table of contents CMK2000 Operating Instructions, 11/2015, A5E34877550B/001...
  • Page 9: Introduction

    The following knowledge is required in order to understand the operating instructions: ● Knowledge in application of the KNX bus system for building automation ● Knowledge of the Siemens LOGO! 8 logic module ● General knowledge in the field of automation technology ●...
  • Page 10 1.1 Preface Naming conventions and abbreviations The term "CMK2000" or "device" is sometimes used in this documentation instead of the full product name "LOGO! CMK2000 KNX module". If "LOGO! 8" is meant, only the term "LOGO!" is used. CMK2000 Operating Instructions, 11/2015, A5E34877550B/001...
  • Page 11: Safety Notes

    The device contains no user-serviceable parts. May cause death or serious injury Unauthorized opening or improperly performed repairs can cause considerable damage to property and/or danger to users. In the case of faults, please contact Siemens Support (Page 86). CMK2000...
  • Page 12 Safety notes 2.1 Safety instructions Safety extra-low voltage Note Only connect the device via a safety extra-low voltage The device is designed for operation using directly connectable safety extra-low voltage (SELV) with safe electrical isolation according to IEC 60950-1 / EN 60950-1 / VDE 0805-1. The following applies to use in North America: The power supply unit for supplying the device with power must comply with NEC Class 2 in accordance with National Electrical Code (ANSI / NFPA 70).
  • Page 13: Security

    Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept.
  • Page 14 Safety notes 2.2 IT security CMK2000 Operating Instructions, 11/2015, A5E34877550B/001...
  • Page 15: System Overview

    System overview Field of application Image 3-1 LOGO! 8 and CMK2000 The CMK2000 is a communication module from the LOGO! series with KNX interface. The LOGO! 8 can be integrated into the KNX system using the CMK2000. It is then possible to exchange information and data between LOGO! 8 and KNX.
  • Page 16: Features

    System overview 3.2 Features Features ● CMK2000 together with LOGO! allows the use of inexpensive actuators and sensors in the KNX environment ● KNX devices can access the signal states of all inputs and outputs of the LOGO! 8. ● Standard LOGO! functions can be used, e.g.: logic functions, ON/OFF delays. ●...
  • Page 17: System Configuration

    System overview 3.3 System configuration System configuration System configuration The following picture shows a basic system configuration with a CMK2000 as the communication module between LOGO! and KNX. Image 3-2 CMK2000 configuration example Tasks and meanings of the system components The CMK2000 communication module allows the transfer and system-compatible scaling of data between KNX and LOGO!.
  • Page 18: System Requirements

    System overview 3.4 System requirements System requirements System requirements ● LOGO! 8 ● 24 V power supply ● KNX bus ● KNX interface (USB or Ethernet) ● Windows PC (for commissioning, maintenance and diagnostics) ● LOGO! Soft Comfort (for programming user functions) ●...
  • Page 19 System overview 3.4 System requirements Differences between the EIB module and CMK2000 The following table provides an overview of the differences in the performance features of the EIB module and the CMK2000: Performance feature EIB module CMK2000 Comment 2-bit solar protection ✓...
  • Page 20 System overview 3.4 System requirements Bus voltage return/loss ✓ can be separately Bus voltage failure/loss configured for each globally configurable channel Update rate Update rate to LOGO! Update rate to LOGO! synchronous with back- adjustable between 50 plane bus rate and 300 ms in steps of 50 LEDs for status dis- 2 LEDs for status dis-...
  • Page 21: Design

    System overview 3.5 Design Design CMK2000 design Design ① 24 V DC connection ② Status LEDs ③ Functional ground FE connection ④ Ethernet connection (LOGO! 8) ⑤ Programming key / Reset key ⑥ KNX bus connection ⑦ Labeling field for physical address CMK2000 design CMK2000 Operating Instructions, 11/2015, A5E34877550B/001...
  • Page 22: Operator Controls And Display Elements

    System overview 3.6 Operator controls and display elements Operator controls and display elements 3.6.1 Status LEDs The CMK2000 indicates the following operating modes on three LEDs: RUN: CMK2000 status • P1: Connection to LOGO! • KNX: Status of KNX communication •...
  • Page 23 System overview 3.6 Operator controls and display elements Connection status KNX / programming mode / warm restart RUN LED P1 LED KNX LED Meaning No KNX bus connected KNX bus connected Programming mode active Incomplete configuration Meaning of LED icons Icon Meaning LED is off...
  • Page 24: Programming Key / Reset Key

    System overview 3.6 Operator controls and display elements 3.6.2 Programming key / Reset key The key on the front of the CMK2000 has the following functions depending on how long it is pressed: Programming key for assigning the physical address via the •...
  • Page 25: Application Planning

    Application planning General installation guidelines General installation guidelines The following guidelines must be observed when mounting and connecting the CMK2000: ● When connecting the CMK2000, make sure that you observe all applicable and legally binding standards. Adhere to the relevant national and regional regulations when installing and operating the device.
  • Page 26 Application planning 4.2 Installation location NOTICE Damage due to overheating You must comply with all the instructions regarding the installation site and mounting position. Otherwise the device may malfunction or incur permanent damage as a result of overheating. Pollution degree The CMK2000 is designed for pollution degree 2.
  • Page 27: Transportation

    Application planning 4.3 Transportation Transportation The devices must be transported in a clean and dry state, preferably in their original packaging. The transport temperature must be between - 40 °C and + 70 °C. Temperature fluctuations greater than 20 K per hour are not permitted. Storage The devices must be stored in clean and dry rooms, preferably in their original packaging.
  • Page 28 Application planning 4.5 Scope of delivery CMK2000 Operating Instructions, 11/2015, A5E34877550B/001...
  • Page 29: Installing/Mounting

    Installing/mounting Installing the CMK2000 The CMK2000 can be mounted on a 35 mm standard mounting rail according to DIN EN 60715 or on a wall / control panel. Permissible installation positions: Horizontal and vertical. Flat mounting is not permissible. Information on selection of the mounting location and on minimum spacing can be found in chapter Installation location (Page 25).
  • Page 30 Installing/mounting 5.1 Installing the CMK2000 Mounting on a control panel / wall Proceed as follows: ① 1. Move the sliders to the outside until they latch in place. 2. The dimensions for the holes are shown in the following picture. Hole for M4 screw, tightening torque 0.8 Nm to 1.2 Nm.
  • Page 31: Connection

    Connection Safety instructions and guidelines Safety instructions WARNING Risk of electric shock May cause death or serious injury • Voltages > 60 V are present in the control cabinet. Therefore appropriate safety precautions must be taken to prevent contact during commissioning and maintenance work.
  • Page 32: Connecting The Power Supply

    Connection 6.2 Connecting the power supply Connecting the power supply 24 V DC power supply The power supply to the CMK2000 device is made using an external 24 V DC supply for the LOGO! side. Note The CMK2000 bridges brief voltage interruptions (< 1.5 ms) in its 24 V DC supply without influencing the function.
  • Page 33 Connection 6.2 Connecting the power supply Connection Connect the CMK2000 to the power supply as shown below: 24 V DC connection Description ① Connection using 2-pole screw terminal (0.5 ... 2.5 mm ), max.. torque 0.5 Nm ② M (ground) External lightning protection module An external lightning protection module can be connected upstream into the 24 V DC supply line as protection against high-energy pulses on the lines:...
  • Page 34: Connecting The Functional Ground

    Connection 6.3 Connecting the functional ground Connecting the functional ground Connect the functional ground (e.g. from the standard mounting rail) in order to discharge ① EMI such as bursts or surges to the FE terminal Permissible conductor cross-section: 0.5 ... 6.0 mm ①...
  • Page 35: Connecting The Knx Bus

    Furthermore there is a danger that the cable shield will break. Note We recommend using RJ45 connectors from the Siemens FastConnect system as the plug- in connectors for the Ethernet cabling. Connecting the KNX bus The CMK2000 is connected to the KNX bus using the red/black KNX terminal.
  • Page 36 Connection 6.5 Connecting the KNX bus CMK2000 Operating Instructions, 11/2015, A5E34877550B/001...
  • Page 37: Generation Of User Functions With Logo

    Generation of user functions with LOGO! Software and hardware requirements (LOGO!) Requirements ● A PC is connected to the LOGO! 8. ● The LOGO! Soft Comfort programming software Version V8.0 or later is installed on the Note CMK2000 is not compatible with previous versions of the LOGO! 8. Overview of LOGO! configuration steps Determine/specify IP address of LOGO! The IP address of the LOGO! specified in LOGO! Soft Comfort or on the device is required...
  • Page 38: Compatibility With Logo! 0Ba7 Projects

    Generation of user functions with LOGO! 7.3 Compatibility with LOGO! 0BA7 projects Compatibility with LOGO! 0BA7 projects The following describes how you can proceed with existing LOGO! 0BA7 projects. LOGO! 0BA7 projects can be used further. Changes are only required for the communication direction KNX → LOGO!. Direct writing to analog or digital inputs and outputs by the KNX module is no longer possible.
  • Page 39: Configuring And Commissioning Using Ets

    ● ETS (Version 4 or higher) is installed on the PC. ETS product database The product database for the LOGO! CMK2000 KNX module is available starting with ETS 4 as a knxprod file for downloading. ● http://www.siemens.com/gamma-td (search text "LOGO")
  • Page 40: Programming The Physical Address

    Configuring and commissioning using ETS 8.3 Programming the physical address Programming the physical address Set the device to programming mode using the key on the front of the CMK2000. In this programming mode it is possible to assign (program) the address to the CMK2000 using the ETS.
  • Page 41: General Parameter Assignments

    Configuring and commissioning using ETS 8.4 General parameter assignments General parameter assignments All KNX products can be configured and assigned parameters using the ETS. Depending on the parameter assignments, the device makes available communication objects with standardized data point types (DPT) for data exchange with other KNX devices. The following general settings of the CMK2000 can be parameterized: ●...
  • Page 42 Configuring and commissioning using ETS 8.4 General parameter assignments Note Guideline for setting the update rate • If the cycle time of the LOGO! is overloaded due to a high level of data exchange (high update rate), a larger value must be used for the update rate, e.g. 200 ms. •...
  • Page 43 Configuring and commissioning using ETS 8.4 General parameter assignments Date and time synchronization Two mechanisms are available for date and time synchronization: ● Synchronization of the time used in the KNX network with the time of the LOGO! 8. ● Synchronization of the time used in the LOGO! 8 with the time in the KNX network. Note •...
  • Page 44: Parameter Assignments For The Knx Channels

    Configuring and commissioning using ETS 8.5 Parameter assignments for the KNX channels Parameter assignments for the KNX channels 8.5.1 Data exchange between KNX and LOGO! Data exchange between KNX and LOGO! is carried out using channels. Each of these channels is able to: ●...
  • Page 45: Logo! Data Types, Inputs And Outputs

    Configuring and commissioning using ETS 8.5 Parameter assignments for the KNX channels 8.5.3 LOGO! data types, inputs and outputs Overview The CMK2000 exchanges data with LOGO! via a network connection and thereby directly accesses the variable memory. Inputs/outputs and flags of the LOGO! For all physical inputs and outputs of the LOGO! (I, Q, AI, AQ), as well as for all analog and digital flags, you can specify the number of the object (e.g.
  • Page 46 Configuring and commissioning using ETS 8.5 Parameter assignments for the KNX channels LOGO! variable memories LOGO! also makes data available in the so-called variable memory, e.g. intermediate results or scaled or calculated display values for an HMI panel. For all data types in the variable memory you can specify the address of the variable memory of the LOGO! 8 from which the values are to be read or to which they are to be written.
  • Page 47: Value Update With Data Transfer From Logo! To Knx

    Configuring and commissioning using ETS 8.5 Parameter assignments for the KNX channels 8.5.4 Value update with data transfer from LOGO! to KNX In order to optimize the bus load (message frame rate) on KNX, it is possible to activate sending of values when they change. Each KNX channel can be parameterized such that a KNX message frame is only sent upon certain changes in value.
  • Page 48: Value Scaling Of The Channels

    Configuring and commissioning using ETS 8.5 Parameter assignments for the KNX channels 8.5.5 Value scaling of the channels LOGO! and KNX work internally with different ranges of values. Therefore scaling is required for transferring certain data types between KNX and LOGO!. Linear scaling can be parameterized using two interpolation points.
  • Page 49 Configuring and commissioning using ETS 8.5 Parameter assignments for the KNX channels Linear scaling between two interpolation points Scaling is specified using 2 interpolation points as parameters per channel. The reference values for the interpolation points are specified in the KNX context and in the LOGO! 8 context.
  • Page 50 Configuring and commissioning using ETS 8.5 Parameter assignments for the KNX channels Response with different data widths and/or different signs If the selected data format is insufficient for successful scaling, the value is automatically set to the maximum or minimum value, even though the original value would require a higher or lower value.
  • Page 51: Response Upon Loss Of Knx Bus Voltage

    Configuring and commissioning using ETS 8.5 Parameter assignments for the KNX channels 8.5.6 Response upon loss of KNX bus voltage The response upon loss of the KNX bus voltage can be set for the communication direction KNX to LOGO!. Upon loss of KNX bus voltage Upon loss of the KNX bus voltage, you can specify whether ●...
  • Page 52: Transfer Of Data From Logo! To Knx

    Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX Transfer of data from LOGO! to KNX 8.6.1 Overview Data transfer from LOGO! to KNX The CMK2000 allows the transfer of simple digital values. In addition, the linking of two digital values is used which are defined in KNX as "Key operation with two independent keys"...
  • Page 53: Supported Logo! Data Types

    Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX 8.6.2 Supported LOGO! data types Supported LOGO! data types The following data types are supported for the transfer of data from the LOGO! to KNX: Image 8-5 Data transfer LOGO! →...
  • Page 54 Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX Values from the LOGO! variable memory If a value to be transferred is to be read from the variable memory of the LOGO!, the corresponding byte address must be specified. The following byte addresses are possible: ●...
  • Page 55: Transfer Of 1-Bit Values

    Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX 8.6.3 Transfer of 1-bit values Image 8-7 Data transfer LOGO! to KNX: 1-bit values LOGO! data type Set a 1-bit LOGO! data type as the preselection for the transfer: ●...
  • Page 56: Special Functions: Dimming And Solar Protection

    Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX 8.6.4 Special functions: dimming and solar protection 8.6.4.1 Dimming (1 bit) This function makes it possible to switch lamps or groups of lamps on and off or to adjust their dimming using just one bit in the LOGO!.
  • Page 57 Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX Dimming (long setting 500 ms or more) - DPT 3.007 With long setting, dimming is brighter or darker depending on the object value and the last controlled dimming direction. If the dimming actuator was switched off, long setting results in brighter dimming.
  • Page 58: Dimming (2 Bits) With Stop Message Frame

    Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX 8.6.4.2 Dimming (2 bits) with stop message frame The two configured binary tags can be used together with short setting to switch on or off or, together with long setting, to dim brighter or darker. You can select which binary variable is to be used for switching off and dimming darker or for switching on and dimming brighter.
  • Page 59: Solar Protection Control (1 Bit)

    Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX 8.6.4.3 Solar protection control (1 bit) This function enables you to to lower or raise solar protection, to stop the movement, or to open and close slats using just one binary variable. Image 8-11 Data transfer LOGO! to KNX: Solar protection LOGO! data type...
  • Page 60 Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX Stop or Slats open / close (short setting up to 500 ms) - DPT 1.009 In the case of short setting, a message frame is sent which results in stopping of the drive when the solar protection is moving or, when the solar protection is stationary, results in a short movement step opposite to the previous direction of movement saved in the moved object.
  • Page 61: Solar Protection Control (2 Bits)

    Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX 8.6.4.4 Solar protection control (2 bits) The two configured binary tags can be used together with long setting to raise or lower the solar protection up to the respective end position or, together with short setting, to terminate the movement or to adjust the slats by one step.
  • Page 62 Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX Slats open / close (short setting up to 500 ms) - DPT 1.009 The "Stop" or "Slats open / close" commands are sent via the group address linked to this object.
  • Page 63: Transferring Percentage Values

    Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX 8.6.5 Transferring percentage values Percentage values are handled in the LOGO! in the range 0...255. Percentage values DPT 5.001 are frequently used in KNX, where the values for KNX are expected in the range 0...255.
  • Page 64 Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX See also Value scaling of the channels (Page 48) Value update with data transfer from LOGO! to KNX (Page 47) Response after startup of LOGO!, CMK2000 or KNX (Page 51) CMK2000 Operating Instructions, 11/2015, A5E34877550B/001...
  • Page 65: Transferring Integer Values

    Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX 8.6.6 Transferring integer values Image 8-15 Data transfer LOGO! to KNX: Integer values LOGO! data type / KNX data type LOGO! data type KNX data type Analog input 2 bytes unsigned - DPT 7.xxx (default) •...
  • Page 66: Sending Float Values

    Configuring and commissioning using ETS 8.6 Transfer of data from LOGO! to KNX 8.6.7 Sending float values Image 8-16 Data transfer LOGO! to KNX: Float values LOGO! data type / KNX data type LOGO! data type KNX data type 2-byte variable memory 2-byte float value - DPT 9.xxx See also Value scaling of the channels (Page 48)
  • Page 67: Data Transfer Knx To Logo

    Configuring and commissioning using ETS 8.7 Data transfer KNX to LOGO! Data transfer KNX to LOGO! 8.7.1 Overview Data transfer from KNX to LOGO! Function DPT in KNX Configuration in ETS Normal 1 bit The input information DPT 1.xxx Transfer of 1-bit values of the KNX bus is (Page 69) mapped 1:1 to the...
  • Page 68: Supported Knx Data Types

    Configuring and commissioning using ETS 8.7 Data transfer KNX to LOGO! 8.7.2 Supported KNX data types You can use the variable memory and the flags of the LOGO! 8 to exchange data with the KNX bus. Supported KNX data types The following data types are supported for the transfer of data from the KNX bus to the LOGO!: Image 8-17...
  • Page 69: Transfer Of 1-Bit Values

    Configuring and commissioning using ETS 8.7 Data transfer KNX to LOGO! 8.7.3 Transfer of 1-bit values Image 8-19 KNX to LOGO!: Transfer of 1-bit values KNX data type / LOGO! data type KNX data type LOGO! data type 1 bit - DPT 1.xxx Digital flag (default) •...
  • Page 70: Using Digital Inputs Of The Logo! 8 As Monoflop

    Configuring and commissioning using ETS 8.7 Data transfer KNX to LOGO! 8.7.4 Using digital inputs of the LOGO! 8 as monoflop The monoflop response can be used to map a digital trigger of KNX in the LOGO! 8 direction as a signal with defined duration. The monoflop can be retriggered, i.e.
  • Page 71 Configuring and commissioning using ETS 8.7 Data transfer KNX to LOGO! Input with monoflop response, preferred state = 0, monoflop time = Tm Image 8-22 Monoflop response: Preferred state = 0 CMK2000 Operating Instructions, 11/2015, A5E34877550B/001...
  • Page 72: Transfer Of Knx Bus State

    Configuring and commissioning using ETS 8.7 Data transfer KNX to LOGO! 8.7.5 Transfer of KNX bus state If the special function "KNX bus state" is configured, the current KNX bus state is transferred directly to the LOGO!. This means that the value is "1" if communication to KNX is OK. The value is "0"...
  • Page 73: Transferring Percentage Values

    Configuring and commissioning using ETS 8.7 Data transfer KNX to LOGO! 8.7.6 Transferring percentage values Percentage values with DPT 5.001 are transferred to KNX as 1-byte values and must therefore be rescaled so that they can be optimally processed further as LOGO! analog values.
  • Page 74: Transferring Integer Values

    Configuring and commissioning using ETS 8.7 Data transfer KNX to LOGO! 8.7.7 Transferring integer values Image 8-25 KNX to LOGO! integer values KNX data type / LOGO! data type KNX data type LOGO! data type 1 byte unsigned - DPT 5.010 1-byte variable memory 1 byte signed - DPT 6.010 1-byte variable memory...
  • Page 75: Sending Float Values

    Configuring and commissioning using ETS 8.7 Data transfer KNX to LOGO! 8.7.8 Sending float values Image 8-26 KNX to LOGO! float values KNX data type / LOGO! data type KNX data type LOGO! data type 2-byte float value - DPT 9.xxx 2-byte variable memory See also Value scaling of the channels (Page 48)
  • Page 76 Configuring and commissioning using ETS 8.7 Data transfer KNX to LOGO! CMK2000 Operating Instructions, 11/2015, A5E34877550B/001...
  • Page 77: Service And Maintenance

    Service and maintenance Diagnostics und maintenance via web The device provides functions for ● Diagnostics ● Updating the firmware via Ethernet communication. Requirements ● Internet Explorer 10 ● Mozilla Firefox portable Version 31 ● Switch Note • The use of cookies must be permitted in the browser •...
  • Page 78 The LEDs shown in the picture correspond to the states described in section Status LEDs (Page 22). If an error has occurred, you can obtain further information on the error codes from Support (http://support.automation.siemens.com). Note • The LED displays may show the current state with a delay depending on the status of the browser and the connection.
  • Page 79: Cleaning

    Service and maintenance 9.2 Cleaning Cleaning The device is designed for maintenance-free operation. ● Nevertheless, clean the surfaces at regular intervals. ● Remove dirt from the enclosure to avoid impairment of the operator control functions and the enclosure ventilation. Disposal The devices described in these instructions can be recycled thanks to their low-pollution design.
  • Page 80 Service and maintenance 9.3 Disposal CMK2000 Operating Instructions, 11/2015, A5E34877550B/001...
  • Page 81: Technical Data

    Technical data 10.1 Dimensional drawing 10.1.1 Dimensional drawing Image 10-1 Dimensional drawing of the CMK2000 CMK2000 Operating Instructions, 11/2015, A5E34877550B/001...
  • Page 82: Technical Specifications

    Technical data 10.2 Technical specifications 10.2 Technical specifications 10.2.1 Technical specifications Technical specifications 6BK1700-0BA20-0AA0 General information Firmware version FW update possible • Installation type/mounting Installation On 35 standard mounting rail, 4 WM Supply voltage Rated value (DC) 24 V 12 V DC •...
  • Page 83 Technical data 10.2 Technical specifications 6BK1700-0BA20-0AA0 Web server Supported Interrupts/diagnostics/status information Diagnostics indicator LED RUN/STOP LED Emission of radio frequency interference according to EN 55 011 Limit class B, for use in residential areas Yes; to EN 61000-6-3 Degree of protection and protection class Degree of protection to EN 60529 IP20 •...
  • Page 84 Technical data 10.2 Technical specifications CMK2000 Operating Instructions, 11/2015, A5E34877550B/001...
  • Page 85: Appendix

    Declaration of Conformity The EC Declaration of Conformity is kept available for the responsible authorities in accordance with the above-mentioned EC Directive at the following address: SIEMENS AG DF FA BRESLAUER STR. 5 90766 FUERTH...
  • Page 86: Service & Support

    You can contact the Technical Support experts in Germany at the following number: ● Phone: + 49 (0) 911 895 7222 ● The contact data for Technical Support in other countries can be found in the Siemens contact database (http://w3.siemens.com/aspa_app/).
  • Page 87: Glossary

    KNX operating voltage over this bus cable. LOGO! LOGO! is the universal logic module from Siemens. You can use LOGO! to solve all tasks associated with home and building control installations, e.g. stairway lighting, outdoor lighting, sun blinds, shutters, shop window lighting etc. It additionally offers solutions for control cabinet installations and for the manufacture of machines and appliances, e.g.
  • Page 88 Glossary Physical address Each KNX device in a KNX installation is assigned an unambiguous and unique number, the physical address. This address consists of three numbers separated by periods: ● The first number is the number of the area in which the associated participant is located ●...
  • Page 89: Index

    Index Minimum spacing, 26 Mounting position, 26 Notes, 26 IT security, 13 Approvals, 85 LOGO! Basic knowledge Trademark, 9 Documentation, 9 Notes CE marking, 85 Installation, 26 Certificates and approvals CE marking, 85 Declaration of Conformity, 85 EMC Directive, 85 CMK2000, 21 Purpose Documentation, 9...
  • Page 90 Index CMK2000 Operating Instructions, 11/2015, A5E34877550B/001...