Configuring and commissioning using ETS
8.5 Parameter assignments for the KNX channels
LOGO! variable memories
LOGO! also makes data available in the so-called variable memory, e.g. intermediate results
or scaled or calculated display values for an HMI panel.
For all data types in the variable memory you can specify the address of the variable
memory of the LOGO! 8 from which the values are to be read or to which they are to be
written.
Note
Note that all channels access the same variable memory, i.e. if the same byte address of the
variable memory is specified for the communication direction KNX → LOGO! in two different
channels, the values in the variable memory will be mutually overwritten.
Other devices and the LOGO! 8 can access the same variable memory.
Note
When transferring 1-byte values from KNX to LOGO!, note that the LOGO! processes 2-byte
values.
46
Operating Instructions, 11/2015, A5E34877550B/001