Troubleshooting - FlowLine EchoPod UG06 Series Quick Start Manual

Ultrasonic liquid level transmitter
Hide thumbs Also See for EchoPod UG06 Series:
Table of Contents

Advertisement

#3 - SETTING THE HEIGHT (SENSOR HEIGHT) & #4 - SETTING THE FILL-H (FILL-HEIGHT)
This setting customizes the reading for your installation.
Follow these instructions to set the height and fill height for your tank:
1) In TOP-LEVEL MENU mode, select TANK.
2) Select HEIGHT.
3) Use the UP and DOWN buttons, set the
HEIGHT of your tank.
4) To enter the value, press and hold OK for 3
seconds and release. SAVED will display.
HEIGHT is now set.
5) Select FILL-H.
6) Use the UP and DOWN buttons, set the
HEIGHT of your tank.
7) To enter the value, press and hold OK for 3
seconds and release. SAVED will display.
FILL-H is now set.
8) Select EXIT to return to the TOP-LEVEL MENU.
9) Select RUN to return to Operational Mode.
Note: The Height and Fill Height settings also determine the 4 to 20 mA current span.
The Height setting determines the 4mA position and the Fill-H setting determines the 20 mA position.
#5 - HOW TO SELECT FAIL-SAFE CURRENT OUTPUT (LOST)
In the event the sensor does not receive an echo,
the Fail-Safe Current Output or LOST setting can
be set to output a current of 4mA, 20mA, 21mA,
22mA or HOLD (last known value). During fail-
safe, the display will read LOST.
1) In TOP-LEVEL MENU mode, select SAFE.
2) Select 4mA, 20mA, 21mA, 22mA or
HOLD by holding down OK button.
3) Select EXIT to return to the TOP-LEVEL
MENU.

TROUBLESHOOTING

If you face any issues not addressed in this Quick Start, please refer to the EchoPod
Flowline's website at www.flowline.com.
|
8
®
Manual located on
QS310140 Rev A2