Display Visualization Of Visograph Remote Terminal - Emerson Dixell iChill IC200D EVO Series Installing And Operating Instructions

Table of Contents

Advertisement

9.21.1
Real Time Clock Setup
1. Push MENU key for some seconds until the bottom display shows "Hour" and the top display shows its
value.
2. Push SET one time: the value is blinking
3. Use the Up and Down keys to adjust it. Push SET one time to confirm; automatically the display shows
next parameter
4. Repeat the operations 2. 3. and 4. for all the RTC parameters:
-
Min: minutes (0÷60)
-
UdAy: day of the week (Sun = Sunday, Mon =Monday, tuE =Tuesday, UEd = Wednesday, tHu =
Thursday, Fri =Friday, SAt =Saturday)
-
dAy: day of the month (0÷31)
-
MntH: month (1÷12)
yEAr: year (00÷99)
9.22 HOW TO ENABLE / DISABLE RECOVERY FUNCTION
FUNCTION rEC
enable / disable recovery function:
o
lower display shows (En /diS)
o
press SET key for some seconds
o
En / diS blinks
o
Press arrow keys to modify the status (enable or disable)
o
press SET key to confirm
o
by pressure of arrow keys it is possible to read the status of recovery valves (rEC1 or rEC2
depending on the circuit)

10. DISPLAY VISUALIZATION OF VISOGRAPH REMOTE TERMINAL

10.1 VISUALIZATION AFTER THE POWER ON
The display visualizes the logo Dixell as showed below.
To enter the main visualization press ENTER.
It is possible to read the main information about the firmware version and bin version by pressing
:
-
release firmware of the Ichill 205D / IC207D
-
release firmware of the Visograph V2I820
-
BIN version of the Visograph V2I820
-
date of the BIN of the Visograph
1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
IC200D
26/192

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dixell ichill ic205dDixell ichill ic207d

Table of Contents