Installation - Emerson Dixell iChill IC200D EVO Series Installing And Operating Instructions

Table of Contents

Advertisement

Accuracy:
Note:
59.5 DIGITAL OUTPUTS
Type:
Number of outputs:
Maximum load:
Note:
59.6 OPERATING AND STORAGE TEMPERATURE
Operating temperature:
Storege temperature:
Operating humidity:

60. INSTALLATION

The device must not be installed in environments where the following situations are present:
 Temperature and humidity outside the range stipulated in the data plate. Frequent and sudden
changes in temperature and/or humidity
 Direct sunlight and weathering in general
 High mechanical stress (vibrations and/or knocks)
 Sulphur and ammonia gas, smoke and salt spray that can cause corrosion and/or oxidation
 Presence of flammable or explosive gas
 Dust
 Devices that generate magnetic interference
Position the device inside the electrical panels, paying attention to the following:
 the distance between the device and the electrical power components
 the distance between the device and the power cables
 sufficient passage for the cooling air
Always comply with the laws and regulations applicable in the country where the device is installed.
Always protect the device for it to always be accessible solely by authorised personnel.
In case of malfunctions, always contact the relative distributor for the device to be repaired.
1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
external relay
Out1..Out3: ±2% full scale
The electrical devices controlled by these
analogue outputs must be powered
separately with another transformer (do
not use the same secondary of the
controller's power) in order to prevent the
outputs from malfunctioning or being
damaged.
Relays with NO contacts
5: IC205D model
7: IC207D model
5A(250Vac) SPST 5(2)A
Verify maximum current of the loads and
maximum current of the common line of
the relay (10A max).
There is double insulation between the
digital outputs and the low voltage of the
rest of the circuit.
Do not use different voltages for the
various groups of relays nor within each
group.
-10°C ÷ 55°C
-30°C ÷ 85°C
20% ÷ 85% (not condensing)
IC200D
191/192

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dixell ichill ic205dDixell ichill ic207d

Table of Contents