Alarm relay and buzzer
Alarm relay / buzzer outputs
Origin
Reset relay alarm
Buzzer silencing
The alarm relay is enabled only by configurating the corresponding output resource.

46. MANUAL ALARM PROCEDURE

CONCEPT OF NUMBER OF EVENTS PER HOUR
For some alarms is possible to set a number of alarms per hour:
if the alarm occours a number of time lower than the value set, the alarm is automatic reset
if the alarm occours a number of time equal the value set, the alarm is manual reset
Each hour is divided in 16
1°Int 2°Int 3°Int 4°Int 5°Int 6°Int 7°Int 8°Int 9°Int 10°Int 11°Int 12°Int 13°Int 14°Int 15°Int 16°Int
After the unit start-up, each interval is marked as "not active". During the interval counting, for 255seconds,
if at least an alarm event appears, the interval itself is marked "Active".
Starting from the first interval the instrument calculates the 16 intervals and, at the end, it restats overwriting
from the first.
In this way the last hour is always monitored and counted the active intervals. when the number of active
intervals reaches the threshold set with the corresponding parameter the alarm becomes manual.
By setting the threshold (parameter)=0 the alarm is manual from its first activation while if the threshold=16
the alarm is always automatic .
1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
Alarms still active
Alarms not reset
Whitout alarms
In stand- by or remote ON-O FF if AL42 = 1
By pushing one of the key of the front panel
th
intervals (each interval is 3600 / 16 = 225 seconds).