If the temperature/pressure decreases under the set rC06-rC07 the heat recovery operation is re-enabled.
To avoid long period in wich the heat recovery function is disabled and if the condenser
temperature/pressure within the range rC06-rC07, the units starts counting the delay set in rC08. After this
delay if the decreasing temperature is still within the rC06-rC07 range, the recovery cycle is forced on again.

44. OPERATION RELATED TO THE REAL TIME CLOCK

44.1 REAL TIME CLOCK DISABLED BY DIGITAL INPUT
When the digital input configured as "Operation working mode: by RTC or keyboard" is active, the real time
clock is disabled and all the function involved with the real time clock are disabled.
44.2 "ONLY SUPPLY FAN" WORKING MODE"
This function can be enabled only if the Ichill is provided with internal clock.
If one of the digital input is configured as "Operation mode with supplay fan only" and it is activated, the Ichill
enables only the supply fan (other loads are disabled); the supplay fan works according to the time table
programming (parameters ES01..ES13).
ATTENTION:
When the supply fan is on and the Ichill is forced in STD-BY or remote OFF (by digital input), the supply fan
will be switched off with a CO18 delay.

45. MESSAGES - ALARM CODES

The alarm codes are defined by an alphanumeric code.
Alarm typology:
A = alarm of the unit
b = alarm of the circuit
C = alarm of the compressor
45.1 AUTOMATIC / MANUAL ALARM DESCRIPTION
The menù ALrM allows to read/reset the alarms.
An alarm can be:
 automatic reset: the alarm reset automatically when the cause of the alarm is not present
 manual reset: manual reset is requested
Some alarms are managed by number of events per hour; it is possible to set a number of alarms per hour
after witch the alarm become a manual reset.
Following an example of low pressure alarm:
o
AL05=0
o
0<AL05<16:
o
AL05=16
Compressor overload alarm is managed in a special way:
-
when the number of the alarms per hour is < AL20, the alarm is a manual reset
-
when the number of the event is = AL20, the alarm is manual reset and a password is requested. In
this case the alarm is stored and visible in COtr menu.
If the cause of alarm is already present, the display shows "no" and it is not possible to reset the alarm.
If the cause of alarm is not present, the display shows "Rst" and it is possible to reset the alarm.
1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
the alarm is always manual reset
o
the alarm is automatic if the number of the event is < AL05
o
the alarm is manual if the number of the event is = AL05
the alarm is always automatic reset