Initiate Remote Alarm Test (Service Terminal Interface Only) - Emerson Autochangeover Controllers AC8 User Manual

Emerson autochangeover controllers owner manual
Table of Contents

Advertisement

7.9.10 Initiate Remote Alarm Test (Service Terminal Interface only)

The service phone number is used for remote monitoring by Liebert Global Services. The Service Ter-
minal Interface may be used to test communications between the AC8 and the service modem. This
test will send a "DIAL OUT TEST PASSED" message to the service phone number.
The test is used to simulate an alarm to verify the proper configuration and functioning of the modem
and other communications required for receiving alarms. This simulated alarm bypasses the normal
alarm sequence—the LCD will not flash, the horn will not sound and there will be no record in the
Alarm Log. A message is sent to the service phone number only if the alarm system is set up correctly.
To initiate the remote alarm test:
• Connect to the AC8 either from a remote computer or through the RS232 port (see
A.2 - Connecting to the Service Terminal Interface).
• At the Main Menu, enter 0 (zero—Setup System - Login Required).
• At the Login Menu, enter your password, then press the Enter key.
• At the Setup Menu, enter 7 (Setup System Information).
• At the Setup System Info menu, enter 9 (Initiate Remote Alarm Test).
• At the Initiate Remote Alarm Test menu, shown below, enter 1 to initiate the remote alarm.
Initiate Remote Alarm Test
INITIATE REMOTE ALARM TEST
This command simulates an alarm
to test alarm notification setup
for the service phone number
1=INITIATE REMOTE ALARM TEST
2=RETURN TO SETUP SYSTEM INFO MENU
3=RETURN TO SETUP MENU
4=RETURN TO MAIN MENU
SELECT A NUMBER:1
• At the Simulate An Alarm Condition prompt, enter Y if you wish to proceed or N if you want to
cancel the alarm simulation.
>SIMULATE AN ALARM CONDITION-YES(Y) OR NO(N)?
>[N]
>[
>COMMAND SUCCESSFUL
• After the "Command Successful" message appears, disconnect from the modem—at the top of the
HyperTerminal window, click on Call, then on Disconnect, as shown below.
Disconnect
• Wait for the AC8 to dial out to send a test message.
• To verify whether the test was successful, check the Event Log (see 5.3 - View Event Log) for
one of these two messages: Dial out test passed or Dial out test failed.
NOTE
Also verify that a message was received at the Service Phone Number.
If the test is NOT successful, check the following:
• Modem configuration (see 7.8.1 - Modem Setup - Initialization String)
• Pager configuration (see 7.8.3 - Pager Setup - Pager Number and PIN)
67
System and Control Options
(Service Terminal Interface only)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Liebert ac8

Table of Contents