50. PARAMETERS LIST

Parameter
Description
ST 1
Chiller Setpoint
ST 2
Chiller minimum Setpoint
ST 3
Chiller maximum Setpoint
ST 4
Heat pump setpoint
ST 5
Heat pump minimum Setpoint
ST 6
Heat pump maximum Setpoint
ST 7
Regulation band in chiller mode
ST 8
Regulation band in chiller heat pump
ST 9
Regulation probe selection in chiller
0= Temperature probe NTC for evaporator inlet
1= Temperature probe NTC for evaporator outlet 1
2= Temperature probe NTC for evaporator outlet 2
3= Temperature probe NTC for common evaporator outlet
4= Temperature NTC probe from remote panel 1
5= Temperature NTC probe from remote panel 2
ST 10
Regulation probe selection in heat pump
0= Temperature probe NTC for evaporator inlet
1= Temperature probe NTC for evaporator outlet 1
2= Temperature probe NTC for evaporator outlet 2
3= Temperature probe NTC for common evaporator outlet
4= Temperature NTC probe from remote panel 1
5= Temperature NTC probe from remote panel 2
6= Temperature probe for water common inlet of the condenser
7= Temperature probe for water inlet of the circuit # 1 condenser
8= Temperature probe for water inlet of the circuit # 2 condenser
9= Temperature probe for water outlet of the circuit # 1 condenser
10= Temperature probe for water outlet of the circuit # 2 condenser
11= Temperature probe for water common otlet of the condenser
ST 11
Type of thermoregulation
0= Proportional
1= Neutral zone
Parameter
Description
dP 1
Default read-out of the top display
dP 2
Default read-out of the bottom display
dP 3
Default display read-out configuration top / bottom
0= Configurable
1= Top display: Evaporator IN, Bottom display: Evaporator OUT
2= Top display: Condenser IN, Bottom display: Condenser OUT
3=Top display: temperature/Condensing pressure, Bottom Display:
evaporating pressure
dP 4
Top display default read-out of the remote terminal_1
0= the read-out depends on the paremeters dP01 – dP02 – dP03
1= the read-out shows the NTC probe of the remote panel.
dP 5
Top display default read-out of the remote terminal_2
0= the read-out depends on the paremeters dP01 – dP02 – dP03
1= the read-out shows the NTC probe of the remote panel.
dP 6
Visograph: firs probe visualized
dP 7
Visograph: second probe visualized
dP 8
Visograph: third probe visualized
dP 9
Visograph: fourth probe visualized
dP 10
Visualization in STD-BY
0= "STD-BY"
1= same visualization of dP1 and dP2
2= "OFF"
Parameter
Description
CF 1
Type of unit
0= Air / air Chiller
1= Air / water Chiller
2= Water / water Chiller
1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10
Visualizzazione display
Unità
IC200D
min
max
M. u.
Resolution
ST02
ST03
°C/°F
-50.0
°C
ST01
-58
°F
110
°C
ST01
230
°F
ST05
ST06
°C/°F
-50.0
°C
ST04
-58
°F
110
°C
ST04
230
°F
0.1
25.0
°C
0
45
°F
0.1
25.0
°C
0
45
°F
0
5
0
11
0
1
min
max
M. u.
Resolution
0
16
0
20
0
3
0
1
0
1
0
39
0
39
0
39
0
39
0
2
min
max
M. u.
Resolution
0
2
dec/int
Dec
int
Dec
int
dec/int
Dec
int
Dec
int
Dec
int
Dec
int
144/192