3.
Push the SET key (immediately on the lower display the rSt label is displayed).
Hold pushed the key for some seconds till the "rSt" label starts flashing and the lower display
4.
shows zero.
To exit: push the CLOCK key or wait 30 sec
NOTE: if the SET key is released within 2s, the controller reverts to display the running hours of
the selected loads..

14. Alarm Menu

The controller memorizes the last 20 alarms happened, together with their duration..
To see the alarm codes see par. par. 23.
14.1 How to see the alarms
1.
Push the
2.
The last alarm happened is showed on the Upper display, while the lower display shows its
number.
Push again the o key and the other alarm are displayed starting from the most recent.
3.
4.
To see the alarm duration and push the SET key.
5.
By pushing again the
Alarms erasing.
1.
Enter the Alarm Menu.
2.
To erase the displayed alarm push the "SET" key till the "rSt" label will be displayed in the
Lower Display,
NOTE the running alarms cannot be erased..
3.
To erase the whole Alarm Menu, hold pressed the "SET" key for 10s.

15. Keyboard locking

15.1 How to lock the keyboard
Keep the o and n keys pressed together for more than 3 s the o and n keys.
1.
The "POF" message will be displayed and the keyboard is locked. At this point it is only
2.
possible to view the set point or enter the HACCP menu.
15.2 To unlock the keyboard
Keep the o and n keys pressed together for more than 3s till the "POn" flashing message
appears.
16. Use of the programming "HOT KEY "
16.1 How to program a hot key from the instrument (UPLOAD)
1.
Program one controller with the front keypad.
1592001431 XC650CX GB r3.5 21.07.2020