Download Print this page

Real Time Clock Functions; Parameter List - Emerson Dixell Wing XW570L Installing And Operating Instructions

Advertisement

4.3 HOW TO SEE THE MAX TEMPERATURE
1.
Press and release the o key.
2.
The "Hi" message will be displayed followed by the maximum temperature recorded.
3.
By pressing the o key or waiting for 5s the normal display will be restored.
4.4 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
To reset the stored temperature, when max or min temperature is displayed :
1.
Press SET key until "rST" label starts blinking.
N.B. After the installation RESET the temperature stored .
4.5 HOW TO SEE AND MODIFY THE SET POINT
1.
Push and immediately release the SET key: the display will show the Set point value;
2.
The SET LED start blinking;
3.
To change the Set value push the o or n arrows within 10s.
4.
To memorise the new set point value push the SET key again or wait 10s.
4.6 TO START A MANUAL DEFROST
1.
Push the DEF key for more than 2 seconds and a manual defrost will start.
4.7 TO ENTER IN PARAMETERS LIST "PR1"
To enter the parameter list "Pr1" (user accessible parameters) operate as follows:
1. Enter the Programming mode by pressing the Set and DOWN key for few
seconds (
2.
The instrument will show the first parameter present in "Pr1"
4.8 TO ENTER IN PARAMETERS LIST "PR2"
To access parameters in "Pr2":
1.
Enter the "Pr1" level.
2.
Select "Pr2" parameter and press the "SET" key.
3.
The "PAS" flashing message is displayed, shortly followed by "0 - -" with a flashing zero.
Use o or n to input the security code in the flashing digit; confirm the figure by pressing "SET". The
4.
security code is "321".
5.
If the security code is correct the access to "Pr2" is enabled by pressing "SET" on the last digit.
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN keys
within 30 seconds.
NOTE: each parameter in "Pr2" can be removed or put into "Pr1" (user level) by pressing "SET" + n. When a
parameter is present in "Pr1" LED
is on.
4.9 HOW TO CHANGE THE PARAMETER VALUE
1. Enter the Programming mode.
2. Select the required parameter with o or n.
3. Press the "SET" key to display its value (
4. Use o or n to change its value.
5. Press "SET" to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key.
NOTE: the new programming is stored even when the procedure is exited by waiting the time-out.
4.10 HOW TO LOCK THE KEYBOARD
1.
Keep the o and n keys pressed together for more than 3 s the o and n keys.
2.
The "POF" message will be displayed and the keyboard is locked. At this point it is only
possible the viewing of the set point or the MAX o Min temperature stored and to switch ON
and OFF the light, the auxiliary output and the instrument.
TO UNLOCK THE KEYBOARD
Keep the o and n keys pressed together for more than 3s.
4.11 ON/OFF FUNCTION
By pushing the ON/OFF key, the instrument shows "OFF" for 5 sec. and the ON/OFF LED is
switched ON.
During the OFF status, all the relays are switched OFF and the regulations are stopped; if a
monitoring system is connected, it does not record the instrument data and alarms.
N.B. During the OFF status the Light and AUX buttons are active.
4.12 TO SEE THE PROBE VALUES
1.
Enter in "Pr2" level.
2.
Select "Prd" parameter with o or n
3.
Press the "SET" key to display "Pb1" label alternate with Pb1 value.
4.
Use o and n keys to display the other probe values.
5.
Press "SET" to move to the following parameter.
1592009130 XW570L GB r1.0 03.08.2015
and
start blinking).
and
LED starts blinking).
5.

REAL TIME CLOCK FUNCTIONS

5.1 TO SEE THE CURRENT TIME AND DAY
1.
Push the n key for more than 3 seconds
e
2.
LED switches ON and the following messages are displayed:
Hur (hour); Min (Minute); dAY (day=giorno)
To exit push n key or wait 5 seconds
3.
5.2 TO SET THE TIME AND THE WEEKLY HOLIDAYS
Push the n key for more than 3 seconds
1.
e
2.
LED switches ON and the current time is displayed.
3.
By pushing the SET key, the
minutes, day and the weekly holidays (up to 3) will be possible.
4.
To exit, press SET + UP or wait 15s without pressing any key.
5.3 TO SET THE DEFROST TIMES
Push the n key for more than 3 seconds
1.
e
2.
LED switches ON and the current time is displayed.
3.
By pushing DEF key, the DEF led will start flashing and setting defrost time will be
possible.
4.
To exit, press SET + UP or wait 15s without pressing any key.
5.4 TO SET THE ENERGY SAVING TIMES
1.
Push the n key for more than 3 seconds
e
2.
LED switches ON and the current time is displayed.
3.
By pushing the ES key, the ES led will start flashing and setting Energy Saving time will be
possible.
4.
To exit, press SET + UP or wait 15s without pressing any key.
5.5 TO START HOLIDAY FUNCTION BY USING THE KEYBOARD
1.
Push the ES key for more than 6 seconds until the label "Hd" is shown.
e
2.
LED will start to blink slower than during time programming and the regulators will
follow holiday times.
3.
Push the ES key for more than 6 seconds to start normal functioning again.
6.

PARAMETER LIST

REGULATION
Hy
Differential: (0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. Compressor
Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set
point.
LS
Minimum set point limit: (-50,0°C
point.
US
Maximum set point limit: (SET
OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of the
instrument and inhibits any output activation for the period of time set in the parameter. (AUX and Light
can work)
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following restart.
CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be used,
for instance, when the room is filled with new products.
Con Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active in case
of faulty thermostat probe. With COn=0 compressor is always OFF.
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is off in case of
faulty thermostat probe. With COF=0 compressor is always active.
DISPLAY
CF
Temperature measurement unit: °C = Celsius; °F = Fahrenheit . When the measurement unit is
changed the SET point and the values of the regulation parameters have to be modified
rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display.
de = 0,1°C; in = 1 °C
Lod Local display : select which probe is displayed by the instrument:
P1 = Thermostat probe; P2 = Evaporator probe; P3 = auxiliary probe
1r2 = difference between P1 and P2 (P1-P2)
Red Remote display : select which probe is displayed by the remote display (XW-REP)
P1 = Thermostat probe; P2 = Evaporator probe; P3 = auxiliary probe
1r2 = difference between P1 and P2 (P1-P2)
DEFROST
tdF Defrost type:
rE = electrical heater (Compressor OFF)
rT = thermostat defrost. During the defrost time "MdF", the heater switches On and OFF depending on the
evaporator temperature and "dtE" value.
in = hot gas (Compressor and defrost relays ON)
EdF Defrost mode:
rtc = Real Time Clock mode. Defrost time follows Ld1÷Ld8 parameters on workdays and Sd1÷Sd8 on
holidays.
in = interval mode. The defrost starts when the time "Idf" is expired.
Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased only when the compressor
is running (even non consecutively) and only if the evaporator temperature is less than the value in "SdF"
(set point for SMARTFROST).
SdF Set point for SMARTFROST: (-30
counting (interval between defrosts) in SMARTFROST mode.
dtE Defrost termination temperature: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator
probe is present) sets the temperature measured by the evaporator probe which causes the end of
defrost.
IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two defrost
cycles.
XW570L
e
LED will start flashing and setting the current hour,
SET; -58°F÷SET) Sets the minimum acceptable value for the set
110°C; SET÷230°F) Set the maximum acceptable value for set point.
30 °C/ -22
86 °F) evaporator temperature which allows the IdF
2/5

Advertisement

loading