Real Time Clock; Serial Communication; User Interface; Information (Read Only) - Emerson Dixell XRB Installing And Operating Instructions

Bottle cooler controller with advanced energy saving algorithms
Table of Contents

Advertisement

7.1.12 REAL TIME CLOCK

Hur
Hours: 0 to 23 hours
Min
Minutes: 0 to 59 minutes
dAY
Day of the week: Sun to Sat
dYM
Day of the month: 1 to 31
Mon
Month: 1 to 12
YAr
Year: 00 to 99
Hd1
First day of weekend: (Sun to SAt; nu) set the first day of the weekend.
Hd2
Second day of weekend: (Sun to SAt; nu) set the second day of the weekend.
Energy saving cycle start time on working days: (00h00min to 23h50min) set the activation
iLE
time of the Energy Saving cycle on working days.
Energy saving cycle duration on working days: (00h00min to 24h00min) set the duration of
dLE
the Energy Saving cycle on working days. NOTE: see the ES paragraph to more information
about interaction with RTC and energy saving mode.
Energy saving cycle start time on weekends: (00h00min to 23h50min) set the activation time
iSE
of the Energy Saving during the weekend.
Energy saving cycle duration on weekends: (00h00min to 24h00min) set the duration of the
dSE
Energy Saving cycle during the weekend.
Daily defrost enabled: (n; Y) to enable the Ld1 to Ld6 defrost operations for any day of the
week.
dd1 = Sunday defrost
dd2 = Monday defrost
dd3 = Tuesday defrost
ddx
dd4 = Wednesday defrost
dd5 = Thursday defrost
dd6 = Friday defrost
dd7 = Saturday defrost
Defrost start time: (00h00min to 23h50min) these parameters set the beginning of the
Ldx
programmable defrost cycles during any ddx day. Example: when Ld2=12.4, the second defrost
starts at 12:40 am during working days.

7.1.13 SERIAL COMMUNICATION

Adr
Serial address: (1 to 247) device address for Modbus communication.
Baudrate: (9.6; 19.2) 9.6=9600baud; 19.2=19200baud. Select the correct baudrate for serial
bAU
communication.

7.1.14 USER INTERFACE

OFF button configuration (right lower side): nu=not used; oFF=ON/OFF function; ES=energy
onC
saving mode activation and deactivation.
OFF button timed (3sec) configuration (right lower side): nu=not used; oFF=ON/OFF
on2
function; ES= energy saving mode activation and deactivation.
Light button configuration (left upper side): nu=not used; Lig=light output; AUS=auxiliary
LGC
output; Lnt=change configuration
Light button timed (3sec) configuration (left upper side): nu=not used; ErA=reset energy
LG2
saving pattern; Lnt=change configuration.
AUS or ES button configuration (left middle side): nu=not used; Pb2=Probe Pb2 visualization;
ESC
AUS=auxiliary output; ES=energy saving mode activation and deactivation.
DEFROST or ES button timed (3sec) configuration (left middle side): nu=not used;
ES2
dEF=defrost activation; AUS=auxiliary output; ES=energy saving mode activation and
deactivation
dnC
DOWN button configuration: nu=not used; Std=standard functions; Lnt=change configuration.
DOWN button configuration: nu=not used; Std=standard functions; Lnt=change configuration;
dn2
Pdn=Pull Down activation.

7.1.15 INFORMATION (READ ONLY)

d1
Probe P1 value visualization
d2
Probe P2 value visualization
d3
Probe P3 value visualization
d4
Probe P4 value visualization
1592038420 XRB30-60-70-77CH EN v1.1 2021.09.15
XRB
15/38