Real Time Clock Functions; Parameter List - Emerson Dixell Wing XW570K Installing And Operating Instructions

Advertisement

4.3
HOW TO SEE THE MAX TEMPERATURE
o
1.
Press and release the
2.
The "Hi" message will be displayed followed by the maximum temperature recorded.
o
3.
By pressing the
key or waiting for 5s the normal display will be restored.
4.4
HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
To reset the stored temperature, when max or min temperature is displayed :
1.
Press SET key until "rST" label starts blinking.
N.B. After the installation RESET the temperature stored .
4.5
HOW TO SEE AND MODIFY THE SET POINT
1.
Push and immediately release the SET key: the display will show the Set point value;
2.
The SET LED start blinking;
3.
To change the Set value push the
4.
To memorise the new set point value push the SET key again or wait 10s.
4.6
TO START A MANUAL DEFROST
1.
Push the DEF key for more than 2 seconds and a manual defrost will start.
4.7
TO ENTER IN PARAMETERS LIST "PR1"
To enter the parameter list "Pr1" (user accessible parameters) operate as follows:
1. Enter the Programming mode by pressing the Set and DOWN key for few seconds
(
and
start blinking).
2.
The instrument will show the first parameter present in "Pr1"
4.8
TO ENTER IN PARAMETERS LIST "PR2"
To access parameters in "Pr2":
1.
Enter the "Pr1" level.
2.
Select "Pr2" parameter and press the "SET" key.
3.
The "PAS" flashing message is displayed, shortly followed by "0 - -" with a flashing zero.
o or n
4.
Use
to input the security code in the flashing digit; confirm the figure by pressing "SET". The
security code is "321".
5.
If the security code is correct the access to "Pr2" is enabled by pressing "SET" on the last digit.
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN keys
within 30 seconds.
NOTE: each parameter in "Pr2" can be removed or put into "Pr1" (user level) by pressing "SET" +
parameter is present in "Pr1" LED
is on.
4.9
HOW TO CHANGE THE PARAMETER VALUE
1. Enter the Programming mode.
o or n
2. Select the required parameter with
3. Press the "SET" key to display its value (
o or n
4. Use
to change its value.
5. Press "SET" to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key.
NOTE: the new programming is stored even when the procedure is exited by waiting the time-out.
4.10
HOW TO LOCK THE KEYBOARD
o
n
1.
Keep the
keys pressed together for more than 3 s the
and
2.
The "POF" message will be displayed and the keyboard is locked. At this point it is only
possible the viewing of the set point or the MAX o Min temperature stored and to switch ON
and OFF the light, the auxiliary output and the instrument.
TO UNLOCK THE KEYBOARD
o
n
Keep the
keys pressed together for more than 3s.
and
4.11
ON/OFF FUNCTION
By pushing the ON/OFF key, the instrument shows "OFF" for 5 sec. and the ON/OFF LED is
switched ON.
During the OFF status, all the relays are switched OFF and the regulations are stopped; if a
monitoring system is connected, it does not record the instrument data and alarms.
N.B. During the OFF status the Light and AUX buttons are active.
4.12
TO SEE THE PROBE VALUES
1.
Enter in "Pr2" level.
o
n
2.
Select "Prd" parameter with
or
3.
Press the "SET" key to display "Pb1" label alternate with Pb1 value.
o
n
4.
Use
and
keys to display the other probe values.
5.
Press "SET" to move to the following parameter.
5.

REAL TIME CLOCK FUNCTIONS

5.1
TO SEE THE CURRENT TIME AND DAY
n
1.
Push the
key for more than 3 seconds
e
2.
LED switches ON and the following messages are displayed:
Hur (hour); Min (Minute); dAY (day = giorno)
o
3.
To exit push
key or wait 5 seconds
1592009630 XW570K GB r1.0 04.08.2015
key.
o or n
arrows within 10s.
.
and
LED starts blinking).
o
.
5.2
TO SET THE TIME AND THE WEEKLY HOLIDAYS
1.
2.
3.
4.
5.3
TO SET THE DEFROST TIMES
1.
2.
3.
4.
5.4
TO SET THE ENERGY SAVING TIMES
1.
2.
3.
4.
5.5
TO START HOLIDAY FUNCTION BY USING THE KEYBOARD
1.
2.
3.
6.

PARAMETER LIST

REGULATION
Hy
Differential: (0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. Compressor Cut
IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set point.
LS
Minimum set point limit: (-50,0°C
point.
n
US
Maximum set point limit: (SET
. When a
OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of the
instrument and inhibits any output activation for the period of time set in the parameter. (AUX and Light
can work)
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following restart.
CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be used,
for instance, when the room is filled with new products.
Con Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active in case
of faulty thermostat probe. With COn=0 compressor is always OFF.
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is off in case of
faulty thermostat probe. With COF=0 compressor is always active.
DISPLAY
CF
Temperature measurement unit: °C = Celsius; °F = Fahrenheit . When the measurement unit is
changed the SET point and the values of the regulation parameters have to be modified
n
keys.
rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display.
and
de = 0,1°C
in = 1 °C
Red Remote display : select which probe is displayed by the remote display (T850)
P1 = Thermostat probe
P2 = Evaporator probe
P3 = auxiliary probe
1r2 = difference between P1 and P2 (P1-P2)
DEFROST
tdF Defrost type:
rE = electrical heater (Compressor OFF)
rT = thermostat defrost. During the defrost time "MdF", the heater switches On and OFF depending on the
evaporator temperature and "dtE" value.
in = hot gas (Compressor and defrost relays ON)
EdF Defrost mode:
rtc = Real Time Clock mode. Defrost time follows Ld1÷Ld8 parameters on workdays and Sd1÷Sd8 on
holidays.
in = interval mode. The defrost starts when the time "Idf" is expired.
Sd = Smart Defrost mode. The time IdF (interval between defrosts) is increased only when the
compressor is running (even non consecutively) and only if the evaporator temperature is less than the
value in "SdF" (set point for SMARTFROST).
SdF Set point for SMARTFROST: (-30
counting (interval between defrosts) in SMARTFROST mode.
dtE Defrost termination temperature: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator
probe is present) sets the temperature measured by the evaporator probe which causes the end of
defrost.
IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two defrost
cycles.
MdF (Maximum) duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the defrost
duration, when P2P = y, defrost end based on temperature, it sets the maximum length for defrost.
dFd Display during defrost:
rt = real temperature;
it = temperature reading at the defrost start;
Set = set point;
dEF = "dEF" label;
XW570K
n
Push the
key for more than 3 seconds
e
LED switches ON and the current time is displayed.
e
By pushing the SET key, the
LED will start flashing and setting the current hour,
minutes, day and the weekly holidays (up to 3) will be possible.
To exit, press SET + UP or wait 15s without pressing any key.
n
Push the
key for more than 3 seconds
e
LED switches ON and the current time is displayed.
By pushing DEF key, the DEF led will start flashing and setting defrost time will be
possible.
To exit, press SET + UP or wait 15s without pressing any key.
n
Push the
key for more than 3 seconds
e
LED switches ON and the current time is displayed.
By pushing the ES key, the ES led will start flashing and setting Energy Saving time will be
possible.
To exit, press SET + UP or wait 15s without pressing any key.
Push the ES key for more than 6 seconds until the label "Hd" is shown.
e
LED will start to blink slower than during time programming and the regulators will
follow holiday times.
Push the ES key for more than 6 seconds to start normal functioning again.
SET; -58°F÷SET) Sets the minimum acceptable value for the set
110°C; SET÷230°F) Set the maximum acceptable value for set point.
30 °C/ -22
86 °F) evaporator temperature which allows the IdF
2/6