6.3 Operation for Replacing/Removing the Control Unit

Replacing the Control Unit due to its Failure
Operation of Control unit
Connect the parent terminal of control unit
and the computer with a LAN cable.
Control unit operation
Set the STOP/RUN switch of the unit to STOP.
Turn off the power and external power
supply for contact output of every control
unit in the system.
Replace the failing control units.
Connect the lithium battery to the replaced
control unit.
Refer to
4.3.6 Connecting/Replacing
the Lithium Battery.
Make a one-to-one connection between
the replaced control unit and the
computer with a LAN cable.
Make a one-to-one connection between
the control unit and the computer with a
LAN cable.
Start
Change the control operation state of the control unit to STOP.
It can be changed both from the unit and from the software.
Execute it from either of them.
No
Have you set up the password for
every replaced control unit?
No
Have you set up the network
information for every replaced
control unit?
To the next page
47
Operation of Control Unit Engineering Tool
When the control operation state is changed
to STOP, the output state is as follows.
Control method
Interlocking control
Compressor control
Schedule control
Software operation
Change the control operation state of the unit.
Refer to
7.13 Change of RUN/STOP.
Set up the password of the control unit.
Refer to
10.3 Change of Password.
Yes
Enter the network information for the
replaced control unit.
Refer to
7.5 Setting of Terminals.
Write the network information into the
control unit. Refer to
Network Information.
Yes
Output state
Retention
All OFF
Retention
7.10.1 Writing