<Example of action when the pressure value is both above the upper limit value and below the lower limit value>
<Example of action>
Adjustment operation time: 1 minute
Start delay time:
Control target at
59 min
the start of control
Upper-upper
limit value
Upper limit
value
Lower limit
value
Lower-lower
Priority
limit value
High
Compressor 1
Operation (load)
Compressor 2
Operation (load)
Compressor 3
Operation (load)
Compressor 4
Operation (load)
Low
①A pressure value exceeds the upper-upper limit value. At the next control period (01 min), the compressor 1 will be switched to
the stop mode regardless of the adjustment operation time.
In addition, the compressor 2 with the next highest priority will be switched to the unloaded operating mode.
②The compressor 1 and compressor 2 are switched to the stop mode and unloaded operating mode respectively.
③Since the adjustment operation time is over, the compressor 2 is switched to the stop mode.
The compressor 3 with the highest priority in compressors with the loaded operating mode is targeted and switched to the
unloaded operating mode.
④Since the adjustment operation time is over, the compressor 3 is switched to the stop mode.
Since the pressure value drops below the lower-lower limit value, at the next control period (04 min), the compressor 1 will be
switched to the loaded operating mode regardless of the adjustment operation time and start delay time.
⑤Regardless of the adjustment operation time and start delay time, the compressor 1 is switched to the loaded operating mode.
The compressor 2 with the highest priority in compressors with the stop mode is targeted and it keeps standby mode until the
adjustment operation time is over.
⑥Since the pressure value rises to the lower limit value or more, at the next control period (06 min), the control for compressor 2
will not be executed.
Furthermore, since the pressure value exceeds the upper limit value, at the next control period (06 min), the compressor 4 with
the highest priority will be switched to the unloaded operating mode.
⑦The compressor 4 is switched to the unloaded operating mode.
1 minute
00 min
01 min
02 min
Pressure measured value
Stop
Operation (unload)
03 min
04 min
Stop
Operation (unload)
Stop
80
Adjustment operation time
Start delay time
Measurement value for
determination
05 min
06 min
Operation (load)
Operation (unload)