7.8 Compressor Control

Compressor control is a function that executes energy saving operation by switching the operation modes of a compressor
(loaded operating mode, unloaded operating mode, and stop mode) in order to optimize the pressure of piping.
One control unit in the system controls one compressor's operation mode.
The number of controllable compressors is two to four units.
In order to execute the compressor control, the valid and invalid time periods are set for control execution with the calendar
setting. When the present time of the control unit becomes arbitrary times set in advance, the compressor control is executed.
The control is executed by monitoring the upper/lower limit of piping pressure.
The piping pressure is measured by the analog input unit (Model: EMU4-AX4) connected to the control unit.
According to the result by monitoring the upper/lower limit of measured pressure values, the operation mode of the
compressor is controlled.
<Precautions for connectable/controllable compressors>
This function controls the operation modes of a compressor (loaded operating mode, unloaded operating mode, and
stop mode) by using the three contacts. Therefore, connectable/controllable compressors are limited to the ones that
can move to each operation mode at the corresponding contact state as the following table.
Operation mode of
compressor
Contact
Loaded/Unloaded
Operating
Stop
<Precautions for control unit clock>
The control unit has a built-in clock.
The clock accuracy is five minute per month difference. Check the clock time regularly, and if there is a difference,
adjust the time. For details on how to check the present time, refer to 10.2 Setting of Clock.
<Precautions for pressure measurement>
As a measurement value, a scaling value of pressure measured by the analog input unit (Model: EMU4-AX4) is used.
To set the scaling value, the optional small type display unit (Model: EMU4-D65) is required.
For details on the scaling value, refer to
(Details).
For details on how to set the scaling value, refer to
Manual (Details).
<Flow of compressor control>
Sun Mon Tue Wed Thu
1
8
15
Calendar setting
22
29
March 9, 2020: Valid/invalid time period of compressor control
0:00
(1)
Check the valid and invalid time periods of compressor control set in advance as of the present date.
(2)
During the invalid time period of compressor control, all the compressors stop (the contacts of all the control units are
switched to OFF).
(3)
When the valid time of compressor control comes, all the compressors start (the contacts of all the control units are
switched to ON).
(4)
The compressor control is executed by the upper/lower limit monitoring of measurement values.
(5)
When the invalid time of compressor control comes that is set with the calendar setting, all the compressors stop (the
contacts of all the control units are switched to OFF).
Loaded
operating mode
ON
ON
ON
Energy Measuring Unit Extension Model for Analog Input User's Manual
March 2020
Fri
Sat
2
3
4
5
6
7
9
10
11
12
13
14
16
17
18
19
20
21
23
24
25
26
27
28
30
31
8:00
Invalid
(Control by the upper/lower
(2)
(3)
Caution
Unloaded
Stop mode
operating mode
OFF
ON
ON
Small Type Display Unit for Energy Measuring Unit User's
February 2022
Sun Mon Tue Wed Thu
1
6
7
8
13
14
15
20
21
22
27
28
17:00
Valid
limit monitoring)
(4)
72
OFF
OFF
OFF
Fri
Sat
2
3
4
5
9
10
11
12
16
17
18
19
23
24
25
262
24:00
Invalid
(5)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Emu4-knet

Table of Contents